8 Operation
Maschinenfabrik Reinhausen GmbH 2020
136
3587317/21 EN
TAPCON
®
Also refer to
2
Setting the switching pulse for controlling the motor-drive unit [
2
Displaying and acknowledging events [
8.11 Regulation
The general functions for regulating the on-load tap-changer are described
in this section.
8.11.1 Response to control system disconnection (optional)
If your device is equipped with a connection to a control system (SCADA),
you can use the following parameters to set how the device is to behave if
the connection to the control system is interrupted.
This function only works in the REMOTE operating mode.
Settings
Parameters
Control
Name
Value
Control variable
Voltage
Response to SCADA disconnection
No reaction
SCADA disconnection delay time
5 s
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
23.09.2020 09:23
Figure 102: Regulation
1. Go to
Settings > Parameters > On-load tap-changer regulator > Regu-
lation
.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the
Accept
button to save the modified parameter.