8 Operation
Maschinenfabrik Reinhausen GmbH 2020
104
3587317/21 EN
TAPCON
®
8.8.2 Configuring IEC 60870-5-101 (optional)
If you want to use the IEC 60870-5-101 control system protocol, you must
set the following parameters.
Settings
Parameters
IEC 60870-5-101
Name
Value
Serial interface
RS232
Baud rate
9600
Transmission procedure
Unbalanced
Number of link address octets
1
Link address
1
Number of ASDU address octets
1
ASDU address
1
No. of information object address...
1
Number of cause of transmission o...
1
Number of databits
8
Parity
Even
Number of stop bits
1
ASDU single character confirmatio...
Off
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
31.01.2020 13:05
Figure 82: IEC 60870-5-101
1. Go to
Settings > Parameters > System > IEC 60870-5-101
.
2. Select the desired parameter.
3. Set the parameter.
4. Press the
Accept
button to save the modified parameter.
Serial interface
You can use this parameter to select the serial interface for data transmis-
sion. You can select the following options:
▪ RS232
▪ RS485
Baud rate
You can use this parameter to set the serial interface's baud rate. You can
select the following options:
▪ 9600 baud
▪ 19200 baud
▪ 38400 baud
▪ 57600 baud
▪ 115200 baud