![MR TAPCON 260 Operating Instructions Manual Download Page 144](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363144.webp)
10 Messages
Maschinenfabrik Reinhausen 2014
144
2374092/04 EN
TAPCON® 260
Messages
This chapter contains an overview of the device's messages.
Signal inputs
Input
Inscription
Function
UC1/2/3-
X1:12
MOTOR-DRIVE
UNIT IN OPERA-
TION
Motor-drive unit is in operation
UC1/2/3-
X1:11
MOTOR PROTEC-
TIVE SWITCH OFF
Motor protective switch has trig-
gered
IO-X1:31
IO-X1:33
See connection dia-
gram
-
IO-X1:12
AUTO
Activate AUTO mode
IO-X1:11
MANUAL
Activate MANUAL mode
IO-X1:13
RAISE
Raise tap position
IO-X1:14
LOWER
Lower tap position
UC1/2/3-
X1:14...17,
UC1/2/3-
X1:30...33
BCD1...BCD10
BCD tap input signal
IO-X1:29
PARALLEL GROUP
1, or: See connec-
tion diagram
Assign parallel operation group 1
IO-X1:28
PARALLEL GROUP
2, or: See connec-
tion diagram
Assign parallel operation group 2
IO-X1:16/17
See connection dia-
gram
-
Table 50: Signal inputs
Signal outputs
Relay
Inscription
Cause
IO-X1:23
See connection
diagram
-
IO-X1:25
See connection
diagram
-
IO-X1:21
FUNCTION
MONITORING
Signal for
Function monitoring
mes-
sage
IO-X1:10
AUTO
Signal if auto mode is active
IO-X1:09
MANUAL
Signal if manual mode is active
IO-X1:04
-
-
IO-X1:06
TAP DIFFER-
ENCE
Signal if tap position difference of ED1,
ED2, ED3 is greater than or equal to 1
10
10.1
10.2
Summary of Contents for TAPCON 260