![MR TAPCON 260 Operating Instructions Manual Download Page 139](http://html.mh-extra.com/html/mr/tapcon-260/tapcon-260_operating-instructions-manual_1844363139.webp)
9 Fault elimination
Maschinenfabrik Reinhausen 2014
139
2374092/04 EN
TAPCON® 260
Fault elimination
This chapter describes how to eliminate simple operating faults.
General faults
Characteristics/detail
Cause
Remedy
No function
▪
Operating status
LED
does not illuminate
No power supply
Check the power supply
Fuse tripped
Contact Maschinenfabrik Reinhausen
GmbH
Relays chatter
Supply voltage too low
Check the supply voltage
High EMC load
Use shielded cables or external filters
Poor grounding
Check the functional ground
Table 44: General faults
No regulation in AUTO mode
Characteristics/detail
Cause
Remedy
Device control commands
have no effect.
▪
RAISE/LOWER LEDs
light up periodically
LOCAL/REMOTE switch in
motor-drive unit switched to
LOCAL.
Check operating mode and switch to RE-
MOTE if necessary.
No connection
Check wiring as per connection diagram.
Device blocking
Negative power flow
Check current transformer polarity.
Control inputs have duplicate
parameterization.
Check parameterization of control inputs.
A function may only be assigned to one
control input.
A control input is parameter-
ized with
blocking
and a sig-
nal is present at this control
input.
Check parameterization and status of
control input under
Info
(Input/Output Sta-
tus). If necessary, change parameteriza-
tion or deactivate signal source.
NORMset is active, but has
not been started up correctly
Activate operating mode
and perform
a manual tap-change operation using
keys
or
. Then activate operating
mode
.
Device blocking
▪
U<
LED illuminated
Undervoltage blocking active
Check parameters
Device blocking
▪
U>
LED illuminated
Overvoltage blocking active
Check parameters
Device blocking
▪
I>
LED illuminated
Overcurrent blocking active
Check parameters
9
9.1
9.2
Summary of Contents for TAPCON 260
Page 167: ......