7 Control system protocol
Maschinenfabrik Reinhausen 2014
131
2374092/04 EN
TAPCON® 260
Attribute
name
Attribute
type
Explanation
M/O/E/C
Remarks
LDCX
ASG
Line drop voltage due to line re-
actance component (voltage)
O
Unit: V
Multiplier: none
BlkLV
ASG
Control voltage below which au-
to lower commands blocked
(relative)
O
Unit: none
Multiplier: c
LimLodA
ASG
Limit load current (LTC block
load current, percentage)
O
Unit: none
Multiplier: c
LDC
SPG
Line drop compensation is R
and X or Z model (0=R and X,
1=Z compensation)
O
-
TmDlChr
SPG
Time delay linear or inverse
characteristic (0=lin., 1=inv.)
O
-
LDCZ
SPG
Line drop voltage due to line to-
tal impedance (percentage of
nominal voltage)
O
Unit: none
Multiplier: c
TapBlkR
ING
Tap position of on-load tap
changer where automatic raise
commands are blocked
O
-
TapBlkL
ING
Tap position of on-load tap
changer where automatic lower
commands are blocked
O
-
Table 35: ATCC class (ATCC1)
YLTC1
Attribute name
Attribute type
Explanation
M/O/E
Remarks
YLTC1
-
OLTC
-
-
Common logical node information
Mod
INC
Mode
O
status only
Beh
INS
Behavior
M
-
Health
INS
Health
O
1 = OK; 2 = signaling
YELLOW for
TAPGUARD; 3 = no
internal communica-
tion of parameter error
or signaling RED for
TAPGUARD
NamPlt
LPL
Name plate
O
Controls
TapChg
BSC
Change tap position
C
direct with normal se-
curity
Measured values
-
-
-
-
-
Status information
7.2.4