7 Functions and settings
Maschinenfabrik Reinhausen 2014
76
222/08 EN
TAPCON® 240
To activate/deactivate the active-power-dependent desired value adjustment
via an input, you have to activate the REMOTE operating mode. The active-
power-dependent desired value adjustment is activated when there is a volt-
age (ON) at the input. If there is no voltage at the input, active-power-de-
pendent desired value adjustment is deactivated and the desired value set
on the device is used.
You can only perform this alternative activation if you have cards with the
necessary configuration. More detailed information can be found in the con-
nection diagram provided. The inputs can be adjusted later on. Contact Ma-
schinenfabrik Reinhausen about this.
If you activate/deactivate the active-power-dependent desired value adjust-
ment via an input, you can no longer activate/deactivate this function via the
display.
To activate/deactivate the active-power-dependent desired value adjustment
via an input, proceed as follows:
1.
Press
to activate remote operation.
2.
Apply voltage via the intended input in accordance with the connection
diagram.
The following sections describe how to set the other parameters.
Activating/deactivating parameters via SCADA
Depending on configuration, you can activate/deactivate the active-power-
dependent desired value adjustment with the aid of a command via SCADA.
More detailed information can be found in the connection diagram provided.
To activate/deactivate active-power-dependent desired value adjustment via
SCADA, proceed as follows:
1.
Press
to activate remote operation.
2.
Send command to device in accordance with protocol specification.
The following sections describe how to set the other parameters.
Setting minimum/maximum desired value
You can use these parameters to set the maximum and minimum desired
value. The maximum or minimum desired value is activated when the meas-
ured active power reaches the set minimum or maximum active power.
You can enter the values in V or in kV. It is only possible to change from V
to kV if all the transformer data have previously been entered.