![MR tapcon 240 Operating Instructions Manual Download Page 17](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358017.webp)
3 Product description
Maschinenfabrik Reinhausen 2014
17
222/08 EN
TAPCON® 240
+
LOCAL
+
REMOTE
+
LOCAL
+
REMOTE
Tap-change operation
using SCADA*
No
No
No
Yes
Value adjustment using
SCADA*
No
Yes
No
Yes
Table 4: Overview of operating modes
*) Optional when connecting TAPCON® to a control system (SCADA)
Hardware
The individual assemblies are fitted in a standardized 19-inch plug-in hous-
ing. The front panels of the assemblies are secured to the plug-in housing at
the top and bottom. An IEC 60603-2 plug connector provides the electrical
connection.
The assemblies are connected to one another via a data bus and direct cur-
rent (DC) supply. This allows for an upgrade with additional plug-in modules
and extension cards at a later date.
Figure 2: Front view
1
Operating panel with display
and LEDs
3
19-inch plug-in housing (in ac-
cordance with DIN 41494 Part
5)
2
Rack for optional expansions
4
Name plate
Name plate
The name plate is on the outside of the device:
3.5
3.5.1