13 Technical data
Maschinenfabrik Reinhausen 2014
160
222/08 EN
TAPCON® 240
Voltage measurement and current measurement
MI
MI3-G
Measurement
1 phase
3 phase
Voltage measure-
ment
U
N
: 100 V AC
Measuring range: 85...140 V AC
Rated frequency: 45...65 Hz
Intrinsic consumption: < 1 VA
Measurement category IV in accordance with
IEC 61010-2-30
Measuring error: < 0.3 % ± 40 ppm/°C
Current measure-
ment
I
N
: 0.2 / 1 / 5 A
Measuring range: 0.01...2.1 · I
N
Rated frequency: 45...65 Hz
Intrinsic consumption: < 1 VA
Overload capacity: 2.1 · I
N
(continuously), 40 x
I
N
/ 1 s
Measuring error: < 0.5 % ± 40 ppm/°C
Phase angle
Measuring accuracy: ± 1°
Frequency measure-
ment
f
N
: 50 / 60 Hz
Measuring range: 45...65 Hz
Measuring accuracy: ± 1 Hz
Table 50: Voltage measurement and current measurement
Interfaces
Interface
Pin
Description
1
Voltage transformer
2
Voltage transformer
5
Shared return conductor
6
Current transformer with rated current
of 5 A
9
Current transformer with rated current
of 1 A
10
Current transformer with rated current
of 0.2 A
Table 51: MI card terminal X1
13.3