![MR tapcon 240 Operating Instructions Manual Download Page 158](http://html.mh-extra.com/html/mr/tapcon-240/tapcon-240_operating-instructions-manual_1844358158.webp)
13 Technical data
Maschinenfabrik Reinhausen 2014
158
222/08 EN
TAPCON® 240
Technical data
Indicator elements
Display
LCD, monochrome, graphics-capable
128 x 128 pixels
LEDs
15 LEDs for operation display and messages
Table 46: Indicator elements
Power supply
SUH-P
Permissible voltage
range
88...264 V AC
88...353 V DC
U
N
: 100...240 V AC
U
N
: 88...353 V DC
Permissible frequency
range
50/60 Hz
Input current
Max. 1 A
Power consumption
35 VA
Internal fuse
250 V; 3 A; 6.3 x 32 mm, "delayed-action" char-
acteristics
Table 47: Standard model
Figure 107: Internal fuses of SUH-P card
F1
Fuse
F2
Spare fuse
13
13.1
13.2
Summary of Contents for tapcon 240