Voltage RegulatorTAPCON® 230
Quick Guide
4831166/00
Page 1: ...Voltage Regulator TAPCON 230 Quick Guide 4831166 00 ...
Page 2: ... for compensation All rights reserved in the event of the granting of patents utility models or designs The product may have been altered since this document was published We reserve the right to change the technical data design and scope of supply Generally the information provided and agreements made when processing the individual quotations and orders are binding The original operating instruct...
Page 3: ...rdware 8 3 1 Operating controls 8 3 2 Display elements 10 4 Functions and settings 13 4 1 Setting the language 13 4 2 NORMset 14 4 3 Control parameters 17 4 3 1 Setting desired value 1 3 17 4 3 2 Selecting a desired value 18 4 3 3 Setting delay time T1 19 4 3 4 Setting control response T1 20 4 3 5 Setting delay time T2 21 4 4 Information about device 22 ...
Page 4: ...Table of contents 4 5 Overview of parameters 24 ...
Page 5: ...rer The product is manufactured by Maschinenfabrik Reinhausen GmbH Falkensteinstraße 8 93059 Regensburg Germany Tel 49 9 41 40 90 0 Fax 49 9 41 40 90 7001 E mail sales reinhausen com Further information on the product and copies of this technical file are available from this address if required Completeness This technical file is incomplete without the supporting documentation Supporting documents...
Page 6: ...rds and guidelines as well as specifications on accident preven tion and environmental protection in the respective coun try of use Safekeeping This technical file and all supporting documents must be kept ready at hand and accessible for future use at all times 1 4 ...
Page 7: ...nce guide contains information that will provide a rapid introduction to operating the voltage regulator For detailed operation and safety information please read carefully through the voltage regulator operating instructions Pay particular attention to the information in the chapter on safety in the operating instructions 2 ...
Page 8: ...3 Hardware 8 Hardware Operating controls The device has 15 pushbuttons The illustration below is an overview of all the device s operating controls 3 3 1 ...
Page 9: ...for lower tap change to the motor drive unit in manual mode REMOTE key Activate deactivate Remote operating mode When you deactivate this operating mode the Local operating mode is automatically activated MANUAL key Activate Manual mode operating mode AUTO key Activate Auto mode operating mode PREV key Change measured value display and switch to previous parameters ...
Page 10: ...tion and save modified pa rameters ESC key Escape current menu and select previous menu levels MENU key Select main menu F1 to F5 function keys Select functions displayed on the screen Display elements The device has a graphics display and 15 LEDs which indicate the various operating statuses or events 3 2 ...
Page 11: ...ely assigned yellow green 2 Overcurrent blocking LED red 10 LED 4 function can be freely assigned yellow red 3 Undervoltage blocking LED red 11 Graphics display 4 Overvoltage blocking LED red 12 Auto operating mode ac tive LED 5 Parallel operation active LED green 13 Manual operating mode active LED ...
Page 12: ...and TAPCON 230 expert 6 NORMset active LED green 14 Remote operating mode active LED 7 LED 1 function can be freely assigned yellow 15 Lower tap change active LED 8 LED 2 function can be freely assigned yellow 16 Raise tap change active LED ...
Page 13: ...ing out the parameterization proceed as fol lows 1 If necessary press and at the same time to deactivate the key lock 2 Press to select manual mode 3 Press to select the main menu ð The parameters can be set Setting the language You can use this parameter to set the display language for the device The following languages are available English Italian German Portuguese French Russian Spanish To set...
Page 14: ...or quickly starting voltage regu lation In NORMset mode the bandwidth and delay time parameters are automatically adapted to the require ments of the grid Line drop compensation cannot be performed in NORMset mode Set the following parameters to operate the device in NORMset mode Activating deactivating NORMset You can use this parameter to activate NORMset mode 4 2 ...
Page 15: ...activate deactivate NORMset mode 1 NORMset ð NORMset activation 2 Press or to activate NORMset by selecting On or to deactivate NORMset by selecting Off 3 Press ð NORMset is activated deactivated Setting the primary voltage With this parameter you can set the voltage transform er s primary voltage Proceed as follows to set the primary voltage 1 NORMset Press until the desired parameter is displaye...
Page 16: ...rameter is displayed ð Secondary voltage 2 Press to increase the value or to reduce it 3 Press ð The secondary voltage is set Setting desired value 1 With this parameter you can set the desired value for au tomatic voltage regulation You can enter the desired val ue as follows In V The value relates to the secondary voltage of the voltage transformer In kV The value relates to the primary voltage ...
Page 17: ...s until the desired parameter is displayed ð Desired value 1 2 Press to increase the value or to reduce it 3 Press ð The desired value is set Control parameters Setting desired value 1 3 You can set up to 3 desired voltage values Desired val ue 1 is the default desired value Desired values 2 and 3 are activated if there is a continuous signal at factory pre set control inputs 4 17 or X4 18 4 3 4 3...
Page 18: ...you want V or kV 3 Press to highlight the position ð The desired position is highlighted and the value can be changed 4 Press to increase the value or to reduce it 5 Press ð The desired value is set Selecting a desired value You can use this parameter to select the active desired value 1 2 or 3 If you select the desired value using appropriately con figured GPIs this parameter s setting is ignored...
Page 19: ...ive Setting delay time T1 This function delays the issuing of a tap change com mand for a defined period This prevents unnecessary tap change operations if the tolerance bandwidth is exit ed To set the delay time T1 proceed as follows 1 Parameter Control parameter Press until the desired parameter is displayed ð Delay time T1 2 Press to highlight the position ð The desired position is highlighted ...
Page 20: ...iation Integral Device responds with a variable delay time which is de pendent on the control deviation The greater the control deviation ΔU in relation to the set bandwidth B the shorter the delay time Proceed as follows to set the control response T1 1 Parameter Control parameter Press until the desired parameter is displayed ð Control response T1 2 Press or to set the response you want 3 Press ...
Page 21: ...ameter Press until the desired parameter is displayed ð Delay time T2 2 Press to increase the time or to reduce it 3 Press ð The delay time T2 is set Activating deactivating delay time T2 To activate deactivate the delay time T2 proceed as fol lows 1 Parameter Control parameter Press until the desired parameter is displayed ð T2 activation 2 Press or to activate deactivate T2 3 Press ð The delay t...
Page 22: ...he following information screens are al so displayed Measured values Calculated values Functional reliability of the LEDs LED test Default parameter Memory overview Event overview MIO card digital inputs MIO card digital outputs PIO card digital inputs1 PIO card digital outputs1 PIO card analog input1 Parallel operation1 Data on CAN bus1 Peak memory1 CI card information2 4 4 ...
Page 23: ...4 Functions and settings 23 IEC 61850 card information3 1 Only for TAPCON 230 pro and TAPCON 230 expert 2 Only for TAPCON 230 expert with CI card 3 Only for TAPCON 230 expert with IEC 61850 card ...
Page 24: ...ff Off Desired value 1 49 140 V 100 V Primary voltage 0 9 999 kV 0 kV Secondary voltage 57 123 V 100 V Control parameters Voltage regulation Desired value 1 49 140 V 100 0 V Desired value 2 49 140 V 100 0 V Desired value 3 49 140 V 100 0 Desired value selec tion Desired value 1 Desired value 2 Desired value 3 Desired value 1 Bandwidth 0 5 9 2 00 Delay time T1 0 600 s 40 s Control response T1 T1 li...
Page 25: ...vervoltage U 100 140 110 Overvolt blocking U On Off Off Overcurrent I 50 210 110 Overcurr blocking I On Off On Undercurrent I 0 210 0 Undercurr blocking I On Off Off Neg active power block On Off Off Control parameters Compensation Compensation method LDC Z LDC Line drop compensa tion Ur 25 25 V 0 0 V Line drop compensa tion Ux 25 25 V 0 0 V Z compensation 0 15 0 0 Z comp limit value 0 15 0 0 Conf...
Page 26: ...5 A Unknown Transformer circuit see operating in structions 0 1PH Display kV V kV V V Display A A Configuration General Language See 13 English Regulator ID 0000 Baud rate 9 6 kilobaud 19 2 kilobaud 38 4 kilobaud 57 6 kilobaud 57 6 kilobaud R L pulse duration 0 10 s 1 5 s Operations counter 0 99 999 999 0 Display dimming On Off On Key lock On Off On Function monitoring On Off Off Delay function mo...
Page 27: ...method Circulating reac tive current Mas ter Follower Au to synchroniza tion Circulating reac tive current Parallel operation group None Group 1 Group 2 Group 1 and Group 2 None CAN address 0 16 0 Simplex mode block ing On Off On Circulating reactive current sensitivity 0 100 0 0 Circulating reactive current blocking 0 5 40 20 0 Master follower cur rent blocking Blocking Off Blocking Parallel erro...
Page 28: ... see operating in structions Off GPI 2 X4 14 Off GPI 3 X4 15 Off GPI 4 X4 16 Quick Tap GPI 5 X4 17 Desired value 2 GPI 6 X4 18 Desired value 3 GPI 7 X6 11 ParGroup1 GPI 8 X6 21 ParGroup2 GPO 1 X4 9 Off GPO 2 X4 12 Off GPO 3 X5 91 ParState GPO 4 X5 121 ParError GPO 5 X5 181 Undervoltage GPO 6 X5 211 Overvoltage GPO 7 X5 241 Overcurrent Configuration LED selection LED1 see operating in structions GP...
Page 29: ...uctions Off Analog Val Tap pos min 0 100 0 0 Analog Val Tap pos max 0 100 100 0 Lowest tap position 40 40 0 Highest tap position 40 40 19 Lower tap position blocking 128 128 0 Upper tap position blocking 128 128 40 Tap position limits blocking behavior Off Directional Non directional Off Configuration Setting desired voltage level remotely1 Setting desired volt age level remotely Off 0 4 20 mA pot...
Page 30: ...onfiguration Communication interface2 Communication proto col see operating in structions Modb ASCII Modbus format see operating in structions 8E1 Communication port RS232 RS485 Ethernet OF RS232 Baud rate communica tion 9 6 kilobaud 19 2 kilobaud 38 4 kilobaud 57 6 kilobaud 9 6 kilobaud Network address 0 0 0 0 255 255 255 255 0 0 0 0 TCP port 0 32 767 1 234 OF light on off On Off Off Local SCADA ...
Page 31: ... Communication interface3 Network address 0 0 0 0 255 255 255 255 0 0 0 0 Network mask 0 0 0 0 255 255 255 255 0 0 0 0 Time server address 1 0 0 0 0 255 255 255 255 0 0 0 0 Time server address 2 0 0 0 0 255 255 255 255 0 0 0 0 Gateway 0 0 0 0 255 255 255 255 0 0 0 0 IED name Transmission medium 100Base TX 100Base FX 100BASE TX Table 2 Overview of parameters 1 Only for TAPCON 230 pro and TAPCON 230...
Page 32: ...5 Overview of parameters 32 3 Only for TAPCON 230 expert with IEC 61850 card ...
Page 33: ......