9 Operation
Maschinenfabrik Reinhausen GmbH 2021
85
7817454/02 EN
TAPCON
®
230 Expert
Property
Options
Correction factor
2)
Set the correction factor (m) for the correction of the func-
tion value (x). The corrected function value (y) is:
y = (m * x) + t
Correction offset
2)
Set the offset (t) for the correction of the function value
(x). The corrected function value (y) is: y = (m * x) + t
Table 21: Configuration of the analog inputs and outputs
1)
Only available for GPAI.
2)
Only available for inputs.
You can only change the configuration of the analog inputs if you have a
Parameter Configurator or Administrator role.
When in delivery status, you can log in as the administrator as follows:
▪ User name:
admin
▪ Password:
admin
Creating a backup
You need to create a backup to be able to reset the system in the event that
any incorrect configuration settings are made.
1. Go to
Settings > Export
.
2. Go to the option
Settings
to export a backup copy of the current settings.
3. Select the desired
interface
(USB or PC).
4. Press the
Export
button to start the export.
Configuring GPAI
1. Go to
Settings > GPAI configuration
.
2. Configure properties such as
function
,
signal type
and
card/channel
.
3. Select the
button to configure the values as desired.
4. Press the
Accept
button.
5. Confirm the security prompt with
Save
to save the changes.
9.1.9 Configuring digital inputs and outputs
Upon delivery, the configurable digital inputs and outputs of the device are
configured as follows:
▪ Input: High active
▪ Output: N/O contact (NO)
You can change this configuration if necessary.