6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
47
7817454/02 EN
TAPCON
®
230 Expert
6.4.5 Connecting SCADA
NOTICE
Damage to the device!
Using the wrong data cable may damage the device.
► Only use data cables which comply with the description below.
Depending on the control system used, you have to connect the device with
one of the following versions.
6.4.5.1 Serial interface RS485 (COM-X6)
1. Connect the wires of the shielded cable in pins 7 (Data +), 6 (GND) and 5
(Data-) of the COM-X6 connector.
Figure 29: Connecting wires in pins 7, 6, 5
2. Position the cable shielding, screw it into the shield clamp provided, and
provide strain relief (using a cable tie).
Figure 30: Shield clamp and strain relief
3. Connect the COM-X1 RJ45 interface and the CPU-X4 interface together
using the patch cable.