6 Mounting
Maschinenfabrik Reinhausen GmbH 2021
52
6796573/02 EN
MSENSE
®
VAM
Use oil-resistant versions for all connection cables outside of control cabi-
nets and versions also with additional UV resistance for those outside of
buildings.
Cable
Assembly
Cable type
Conductor cross-sec-
tion
Max. length
Signal inputs
DIO 28-15,
DIO 42-20
Shielded
1.5 mm
2
400 m (<25 Ω/km)
Signal outputs*
DIO 28-15,
DIO 42-20
Shielded
1.5 mm
2
-
Signal inputs
AIO 2, AIO 4,
AIO 8
Shielded
1 mm
2
400 m (<25 Ω/km)
Signal outputs
AIO 2, AIO 4,
AIO 8
Shielded
1 mm
2
-
RS232, SUB-D
CPU I, CPU II
Shielded
0.25 mm
2
25 m
RS485; SUB-D
CPU I, CPU II
Shielded
0.25 mm
2
140 m
Ethernet RJ45
CPU I
Min. CAT5, shielded
S/FTP
-
100 m
Ethernet FO
MC 2-2,
SW 3-3
Duplex LC
Multimode, OM3,
1310 nm
-
2000 m
Table 12: Recommendation for connection cables
*) Observe line capacitance, see note above.
6.3.2 Information about connecting serial interfaces RS232 and RS485
NOTICE
Damage to the device!
Using the wrong data cable may damage the device.
► Only use data cables which comply with the description below.