8 Operation
Maschinenfabrik Reinhausen GmbH 2021
103
6796573/02 EN
MSENSE
®
VAM
Linking SCADA messages
When you link a SCADA message to an event, the device sets the data point
to "On" when the event occurs. When the event stops, the device sets the
data point to "Off". A parameter is available for each available SCADA mes-
sage.
Figure 79: Linking SCADA messages
In order to establish the link, you have to enter the corresponding event
number in the desired parameter.
If you enter event number 500, the link is disabled.
To link the SCADA message, proceed as follows:
ü
The desired event number is known.
1. Go to
Settings > Parameters > Link messages
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
8.7.7 Linking functions
You can link the
Generic digital input
or
Generic SCADA command
events
with device functions. This allows you to remotely control the device using
digital inputs or commands via the control system (SCADA). The following
parameters are available for this purpose: