6 Electrical connection
63
BA6820378-03 EN
6.9 Connecting the RS485 interface and configuring Modbus
(optional)
The MESSKO® MTRAB® can be connected with a SCADA system via the
RS485 interface. This is designed as a 4-conductor system (full duplex), but
can also be integrated into a 2-conductor system (half duplex).
RS485 interface assignment for Modbus RTU
PINs
4-conductor system
2-conductor system
1
Rx+
D+
1
Rx-
D-
2
Tx-
2
Tx+
Shield
Shield
Comm
Comm
6.9.1 4-conductor full duplex
Figure 42: 4-conductor system