5 Mounting
30
BA5789879-01 EN
5.2 Mounting pressure relief device with OD protective cover
In order to mount the device, you must open it. Only close it again once
mounted.
Figure 7: Mounting pressure relief device with OD protective cover
1 4 housing screws M8x100, wrench
size 13
2 Protective cover
3 Signal pin, wrench size 12
4 Signal pin cap, wrench size 32
5 Clearance above: min. 100 mm [4"] / with semaphore 170 mm [6.7"]
Opening the device
Prepare for mounting the device as follows:
1. Remove protective cover (2). To do so, pull out signal pin (3) and screw
off the signal pin cap (4) using 2 open-ended wrenches, wrench size 12
and 32.
2. Then unscrew the 4 screws (1), wrench size 13, from the protective cover.
3. Lift off the protective cover and place it on a stable surface.