6 Mounting
29
5809776/02 EN
▪ The device's connection cables must be laid in close contact with the
grounded metal housing or in metallic cable ducts with a ground connec-
tion.
▪ Signal lines and supply lines / switching lines must be laid in separate ca-
ble ducts.
▪ The device must be grounded at the screw provided using a cable.
6.1.3 Cable recommendation
Please note the following Maschinenfabrik Reinhausen recommendation
when wiring the device.
Cable
Cable type
Conductor cross-
section
Max. length
Power supply
Unshielded
≥ 0.5 mm²
-
Functional ground
Unshielded
≥ 2.5 mm²
-
Ethernet RJ45
Min. CAT5,
shielded S/FTP
-
100 m
Table 9: Cable recommendation
6.1.4 Requirements on the power supply
For the safe operation of the product, observe the following requirements on
the power supply:
▪ Only connect the device to an energy-limited electric circuit in accordance
with IEC 61010-1. When doing so, use a miniature fuse: 250 VDC, 2 A, 5
x 20 mm, characteristic "delayed-action". The voltage source must be iso-
lated.
▪ As an alternative, you may also connect the device to a voltage source
that complies with the requirements of NEC class 2 in accordance with UL
1310.