9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
73
4453918/14 EN
ETOS
®
TD
9 Visualization
The ETOS® TD motor-drive unit is equipped with web-based visualization .
This allows you to configure the device with a computer and to display mea-
sured values.
System requirements
To access the web-based visualization, you need a PC with an HTML5-ca-
pable browser. The display is optimized for the following browsers:
▪ Microsoft® Internet Explorer 10 or higher
▪ Google Chrome™
9.1 Establishing connection to visualization
You can use the ETH1.1 interface or the optional ETH2.2 interface of the
CPU assembly to establish the connection to the visualization. The inter-
faces do not use a DHCP server. Therefore, you must assign a static IP ad-
dress to your PC. To do this, observe the following configuration example:
Interface
Configuration
Standard
ETH1.1
IP address: 192.168.165.1 (not adjustable)
PC
IP address: 192.168.165.100
Subnet mask: 255.255.255.0
Optional
ETH2.2
IP address: 192.0.1.230 (factory setting) [
Subnet mask: 255.255.255.0
PC
IP address: 192.0.1.100
Subnet mask: 255.255.255.0
Table 16: Interface configuration example