9 Visualization
Maschinenfabrik Reinhausen GmbH 2020
118
4453918/14 EN
ETOS
®
TD
Generic digital output X
You can use this parameter to link the digital output with an event message.
To do so, enter the desired event number.
If you enter event number 500, the link is disabled.
9.9.3 Linking control system messages
You can link each event with a control system message. The device pro-
vides 10 SCADA messages for this purpose. When you link a SCADA mes-
sage to an event, the device sets the data point to "On" when the event oc-
curs. When the event stops, the device sets the data point to "Off". A param-
eter is available for each available SCADA message.
To forward control system commands, you need to link the control system
messages to the
Generic digital input
or
Generic SCADA command
events.
Settings
Parameters
Link messages
Name
Value
Generic SCADA status message 1
500
Generic SCADA status message 2
500
Generic SCADA status message 3
500
Generic SCADA status message 4
500
Generic SCADA status message 5
500
Generic SCADA status message 6
500
Generic SCADA status message 7
500
Generic SCADA status message 8
500
Generic SCADA status message 9
500
Generic SCADA status message 10
500
Home
Events
Information
Recorder
Settings
EN
CHANGE
REBOOT
admin
04.02.2020 11:14
Figure 85: Linking SCADA messages
ü
The desired event number is known.
1. Go to
Settings > Parameters > System > Link messages
.
2. Select the desired parameter.
3. Enter the desired event number.
4. Press the
Accept
button to save the modified parameter.
Generic SCADA message X
You can use this parameter to link the SCADA message with an event mes-
sage. To do so, enter the desired event number.