![MR ETOS IM Operating Instructions Manual Download Page 63](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393063.webp)
5 Mounting
Maschinenfabrik Reinhausen GmbH 2019
63
5163667/06 EN
ETOS
®
IM
Connection example MESSKO® MTeC® EPT303 FO
If you would like to use a MESSKO® MTeC® EPT303 FO sensor, you must
connect the sensor to the RS485 plug terminals on the sensor bus. Use a
shielding clamp to apply the shield to the cable. You can directly connect ad-
ditional MESSKO® MTeC® EPT303 FO sensors to the plug terminal.
The EPT303 FO sensor module contains a terminating resistor. If you would
like to use the EPT303 FO sensor together with other sensor types on an
MR sensor bus, then we recommend connecting the EPT303 FO sensor to
the end of the bus.
CPU-COM2
EPT303 FO
D0 (A)
D1 (B)
Com. (C)
1
2
3
4
5
6
7
8
9
D+ (B)
GND
D- (A)
D+ (B)
GND
D- (A)
1
2
3
4
5
6
1
6
Figure 46: Connection example MESSKO® MTeC® EPT303 FO on the MR sensor bus
5.6.4 Information about laying fiber-optic cable
To ensure the smooth transfer of data via the fiber-optic cable, you must en-
sure that mechanical loads are avoided when laying the fiber-optic cable and
later on during operation. Also observe the information from the manufac-
turer of the fiber-optic cable and the following instructions:
▪ Radii must not fall below the minimum permissible bend radii (do not bend
fiber-optic cable).
▪ The fiber-optic cables must not be over-stretched or crushed. Observe the
permissible load values.
▪ The fiber-optic cables must not be twisted.
▪ Be aware of sharp edges because they can damage the fiber-optic cable's
coating during laying or can place mechanical loads on the coating later
on.
▪ Provide a sufficient cable reserve near distributor cabinets. Lay the re-
serve such that the fiber-optic cable is neither bent nor twisted when tight-
ened.