7 Operation
Maschinenfabrik Reinhausen GmbH 2019
245
5163667/06 EN
ETOS
®
IM
7.21.1 Configuring overload
To calculate the overload capability of the transformer, the following parame-
ters must be set.
Figure 190: Configuring overload
Calculation method
You can use this parameter to set the method for calculating the overload.
You can select the following options:
▪ IEC 60076-7
▪ IEEE Std C57.91
To select the calculation method, proceed as follows:
1. Go to
Settings > Parameters > Overload > Calculation method
.
2. Select the desired option.
3. Press the
Accept
button to save the modified parameter.
Limits used
You can use this parameter to set which limit values the device is to use.
You can select the following options:
▪ Medium power
▪ High power
▪ Customized