![MR ETOS IM Operating Instructions Manual Download Page 157](http://html.mh-extra.com/html/mr/etos-im/etos-im_operating-instructions-manual_1844393157.webp)
7 Operation
Maschinenfabrik Reinhausen GmbH 2019
157
5163667/06 EN
ETOS
®
IM
Setting
Behavior
Auto blocking
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ Automatic regulation is blocked.
Auto/manual blocking
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ Automatic regulation is blocked.
▪ You cannot perform tap-change operations in manual
mode.
Target tap position
▪ The
Reversal of power flow
event is issued.
▪ If Z compensation is activated, this function is deacti-
vated.
▪ The device triggers a tap-change operation to the tap
position you defined in the "Target tap posi-
tion" [
Section 7.9, Page 168] parameter.
▪ The device blocks further tap-change operations.
▪ The target-tap-position operation is ignored if there is
no tap-position capture. Automatic regulation is
blocked.
Table 49: Behavior in the event of a reversal of power flow
7.8.5 Tap position monitoring (optional)
You can set 2 limit values for tap position monitoring:
▪ Pos<
▪ Pos>
You can set the following parameters for each limit value.
▪ Delay time (optional)
▪ Behavior limit value
Delay time limit value
You can use this parameter to set the delay time in order to delay the issuing
of the event message.
Summary of Contents for ETOS IM
Page 1: ...Monitoring system ETOS IM Operating instructions 5163667 06 EN ...
Page 410: ......
Page 411: ......