6 Mounting
Maschinenfabrik Reinhausen GmbH 2018
58
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
Suitable equipment includes isolating devices in accordance with IEC
60947-1 and IEC 60947-3 (e.g. circuit breaker). Note the properties of the
relevant circuits (voltage, maximum currents) when selecting the circuit
breaker type. In addition, observe the following:
▪ It must be easy for the operator to access the isolating device
▪ The isolating device must be labeled for the device and circuits to be iso-
lated
▪ The isolating device may not be a part of the power line
▪ The isolating device may not interrupt the main protective conductor
Miniature circuit breaker
You must fuse the power supply circuit with a miniature circuit breaker. The
miniature circuit breaker must have the following properties:
▪ Rated current: 6 to 20 A
▪ Triggering characteristic: B or C
Conductor cross-section
For the power supply circuit, use a conductor cross-section suitable for the
miniature circuit breaker that you have selected, but at least 1.5 mm
2
(AWG
15).
Connecting the voltage supply
To connect the voltage supply, proceed as follows:
► Connect the voltage supply in accordance with the connection diagram
provided.