8 Operation
Maschinenfabrik Reinhausen GmbH 2018
137
5252433/02 EN
ECOTAP
®
VPD
®
CONTROL PRO
8.11.7.2 Configuring IEC 60870-5-103 data points
You can adjust the following data point properties for the IEC 60870-5-103
control system protocol:
Column
Description
Modifiable
Setting range
Active
You can use the checkbox to set whether the data point is
to be transferred via the control system protocol or not.
Yes
Active/inactive
TYP
Data point type code.
No
-
FUN
Data point function type.
Notice: You can only use function type 254 for data points
with type code 10 or 11.
Yes
0...255
INF
Data point information number.
Notice: You can only use information number 0 for data
points with function type 254.
Yes
0...255
GIN
Data point generic identification number.
Notice: You can only use generic identification number 0
for data points with a function type other than 254.
Yes
0...65,535
Data Type
Data point data type.
No
-
Name
Data point designation.
No
-
Interrogation
The value indicates whether the data point is to be in-
cluded in a general query (1) or not (0).
Yes
0, 1
Threshold
Threshold value for measured values. The data point is
only transferred again if the change of value is greater
than the threshold value.
▪ If you enter the value 0, no threshold value is active.
▪ If you do not enter any value, the device adopts the
threshold value defined by the device parameter. If no
device parameter is available for the threshold value,
no threshold value is active either.
Yes
0...1,000,000,000
Table 44: Configuring IEC 60870-5-103 data points
Figure 89: Configuring IEC 60870-5-103 data points