7 Operation
Maschinenfabrik Reinhausen GmbH 2021
78
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
2. Press
to confirm the selection.
ð
3. Press
to confirm the selection.
4. Press
or
to select the desired value.
5. Press
to confirm the selection.
6. Press
to save the setting.
7.4.1.3 Delay time T1 (P2.2)
The delay time T1 delays the issuing of a tap-change command for a de-
fined period. This prevents unnecessary tap-change operations if the toler-
ance bandwidth is exited only briefly.
To set the delay time T1, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
until the desired parameter is displayed.
ð
4. Press
to confirm the selection.
5. Press
or
to select the desired value. Alternative: Press
+
or
+
to set the value in larger steps.
6. Press
to confirm the selection.
7. Press
to save the setting.
7.4.1.4 Bandwidth B2 (P3.1)
You can use this parameter to set the maximum permissible deviation of
measured voltage U
actual
from the desired value U
desired
for fast regulation. En-
sure that the value is always at least 0.5% greater than the bandwidth B1. If
you set a lower value, the device corrects the setting automatically. If you
select the "off" option, fast regulation is deactivated.