7 Operation
Maschinenfabrik Reinhausen GmbH 2021
76
8209941/00 EN
ECOTAP
®
VPD
®
III 30D-24 / MD&C
Figure 50: Regulation function response
1 + B%: Upper limit
2 U
desired
: Desired value
3 - B%: Lower limit
4 Set delay time T
5 U
actual
: Measured voltage
6 B%: Tolerance bandwidth
A U
actual
is outside the bandwidth. De-
lay time T starts.
B U
actual
is back within the bandwidth
before delay time T is complete.
C U
actual
is outside the bandwidth. De-
lay time T starts.
D U
actual
is still outside the bandwidth
when delay time T is complete.
Tap-change operation is initiated.
7.4.1.1 Desired voltage (P1)
You can use this parameter to set the desired value for voltage regulation.
To do so, proceed as follows:
ü
The AVR MANUAL operating mode is active.
1. Press
>
until the desired parameter is displayed.
ð
2. Press
to confirm the selection.
3. Press
or
to select the desired value.
4. Press
to confirm the selection.
5. Press
to save the setting.