background image

1000 kW Containerized

Diesel Generator Set

Standard Features

Cummins Heavy Duty Diesel Engine

4-cycle design, turbocharged, aftercooled, direct injection

Polymide blade cooling fan

Engine coolant heater

Meets  Tier 2 EPA emissions standards

Fuel System

1000 gallon, single wall fuel tank

Fuel priming system

Fuel/water separators and drip pan

Electric fuel pump

External fuel fill

30 micron RACOR

®

 

fuel/water separator with drip pan assembly

Alternator

Brushless, 4-pole, synchronous, WYE connection

Class H insulation system conforms to NEMA MG1-22, BS5000,
CSA-C22-2, IEC-34-1 standards for temperature rise

Separate excitation for fast recovery from block loads and motor
starting

Drip-proof, self-venting, amortisseur windings

Epoxy impregnated windings with tropical insulation for increased
environmental protection and long life

Automatic Voltage Regulator

Circuitry senses true RMS voltage, rather than average, for superior
load regulation

1000 KW

Full Load Acceptance

Accepts 100% of standby nameplate rating in one step, in compliance
with NFPA110 Standards

Generator Control Panel

 BASLER vibration-isolated controller

Manual or remote engine start/stop

RS485/Modbus communication support

Safety shutdowns

Externally mounted emergency stop switch

Generator mainline circuit breaker, electronically operated, UL listed

Specially Designed Container

40 ft. ISO container, sound-attenuated, foam-lined for extremely
quiet operation

Isolated operator control room

Solidly mounted battery rack and cooling system

Intregral vibration isolators

Exterior polyurethane coating system provides long life in extreme
operating conditions

Interior DC lights and timer switch

Crankcase filtration system

Critical grade silencer with heat blankets

Warranty

Engine-generator sets are covered by an express written, one-year
limited warranty

(Shown with 40 ft. container and optional ISO trailer chassis)

Model

Emissions

Standby Rating

Prime Rating

EGC1000C

EPA Certified

60 Hertz

1000kW (1250kVA)

900kW (1125kVA)

EGC1000C  Rev 3

Summary of Contents for EGC1000C

Page 1: ... than average for superior load regulation 1000 KW Full Load Acceptance Accepts100 ofstandbynameplateratinginonestep incompliance with NFPA110 Standards Generator Control Panel BASLER vibration isolated controller Manual or remote engine start stop RS485 Modbus communication support Safety shutdowns Externally mounted emergency stop switch Generator mainline circuit breaker electronically operated...

Page 2: ... EGC1000C Rev 3 Alternator Specifications Model 741RSL4045 Marathon Magna Max Type Rotating Field Number of Leads 10 or 12 Generator Type Rotating Field PMG Voltage Regulator Solid State Digital Model DVR2000 Insulation NEMA MG1 1 66 Material Class H Temperature Rise 105o 125o C Bearing Number Type Single Sealed Coupling Flexible Disk Amortisseur Windings Full Voltage Regulation 0 25 One Step Load...

Page 3: ...y with Filters 35 gal 132 L Local and Remote Generator Control Automatic and manual starting and stopping Engine and Generator Protection Programmable Analog Engine Senders ECU Communications via SAE J1939 16 Programmable Contact Inputs Programmable Logic Automatic Transfer Switch Control Mains Failure Integrated RS485 Modbus Connection Auto Synchronizing Event recording Monitoring Engine RPM Engi...

Page 4: ...Oil Reservoir with Level Control 15 gallon Centrifugal Oil Filter System Oil Pan Heater with Thermostat Alternator Strip Heater AC Battery Charger with Shore Power Receptacle 120VAC Convenience Receptacle Utility Grade Protective Relay Optional Features and Accessories Container ISO Trailer Chassis 40 ft Double wall Fuel Tank 900 gallon capacity Fluid Containment Manual Fuel Valves For Internal or...