3KW/5KW
INVERTER / CHARGER
Version: 1.0
User Manual
PIP-MK SERIES
Page 1: ...3KW 5KW INVERTER CHARGER Version 1 0 User Manual PIP MK SERIES...
Page 2: ...Panel Installation 9 Communication Connection 10 Dry Contact Signal 10 OPERATION 11 Power ON OFF 11 Operation and Display Panel 11 LCD Display Icons 12 LCD Setting 14 Display Setting 22 Operating Mod...
Page 3: ...unit will not reduce this risk 5 CAUTION Only qualified personnel can install this device with battery 6 NEVER charge a frozen battery 7 For optimum operation of this inverter charger please follow r...
Page 4: ...ons via LCD setting Configurable AC Solar Charger priority via LCD setting Compatible to mains voltage or generator power Auto restart while AC is recovering Overload Over temperature short circuit pr...
Page 5: ...nput 8 AC output 9 PV input 10 Battery input 11 Circuit breaker 12 Remote LCD panel communication port 13 Parallel communication cable only for parallel model 14 Current sharing cable only for paralle...
Page 6: ...ng points before selecting where to install Do not mount the inverter on flammable construction materials Mount on a solid surface Install this inverter at eye level in order to allow the LCD display...
Page 7: ...d cable and terminal size as below Recommended battery cable and terminal size Model Typical Amperage Battery Capacity Wire Size Ring Terminal Torque Value Cable mm2 Dimensions D mm L mm 3KW 200A 200A...
Page 8: ...spec of AC breaker is 30A for 3KW 50A for 5KW CAUTION There are two terminal blocks with IN and OUT markings Please do NOT mis connect input and output connectors WARNING All wiring must be performed...
Page 9: ...the proper recommended cable size as below Model Typical Amperage Cable Size Torque 3KW 60A 6 AWG 1 2 1 6 Nm 5KW 80A CAUTION Important Be sure to connect AC wires with correct polarity If L and N wir...
Page 10: ...tage Range 30 115Vdc 60 115Vdc Please follow below steps to implement PV module connection 1 Remove insulation sleeve 10 mm for positive and negative conductors 2 Check correct polarity of connection...
Page 11: ...the bottom case Then pull out the cable from the remote communication port Step 2 Drill two holes in the marked locations with two screws as shown below chart Place the panel on the surface and align...
Page 12: ...0VAC available on the rear panel It could be used to deliver signal to external device when battery voltage reaches warning level Unit Status Condition Dry contact port NC C NO C Power Off Unit is off...
Page 13: ...dicating the operating status and input output power information LCD display Indicators LED Indicator Color Solid Flashing Messages Status indicators Green Solid On Output is available in bypass mode...
Page 14: ...ttery level by 0 24 25 49 50 74 and 75 100 in battery mode and charging status in line mode In AC mode it will present battery charging status Status Battery voltage LCD Display Constant Current mode...
Page 15: ...0 Mode Operation Information Indicates unit connects to the mains Indicates unit connects to the PV panel Indicates load is supplied by utility power Indicates the utility charger circuit is working I...
Page 16: ...ttery provides power the loads SUB Solar first Solar energy provides power to the loads as first priority If solar energy is not sufficient to power all connected loads utility energy will supply powe...
Page 17: ...selected battery charge voltage and low DC cut off voltage can be set up in program 26 27 and 29 06 Auto restart when overload occurs Restart disable default Restart enable 07 Auto restart when over t...
Page 18: ...voltage point back to utility source when selecting SBU SBU priority or SUB Solar first in program 01 3KW default setting 23 0V 5KW default setting 46 0V 3KW model setting range is from 22 0V to 28 5...
Page 19: ...ult Solar energy charges battery first and allow the utility to charge battery SbL Solar energy for battery first UdC Disallow utility to charge battery Solar energy charge battery first and disallow...
Page 20: ...y switches 20 Backlight control Backlight on default Backlight off 22 Beeps while primary source is interrupted Alarm on default Alarm off 23 Bypass function Bypass Forbidden If selected inverter won...
Page 21: ...cut off voltage 3KW default setting 21 0V 5KW default setting 42 0V If self defined is selected in program 5 this program can be set up Setting range is from 20 0V to 27 0V for 3KW model and 40 0V to...
Page 22: ...k is 5 min 37 Equalization interval 30days default Setting range is from 0 to 90 days Increment of each click is 1 day 39 Equalization activated immediately Disable default Enable If equalization func...
Page 23: ...to 59 96 Time setting Hour For hour setting the range is from 00 to 23 97 Time setting Day For day setting the range is from 00 to 31 98 Time setting Month For month setting the range is from 01 to 12...
Page 24: ...rrent charging power battery voltage output voltage output frequency load percentage load in Watt load in VA load in Watt DC discharging current main CPU Version Selectable information LCD display Inp...
Page 25: ...rging current 50A PV charging current 50A AC charging current 50A Charging power AC and PV charging power 500W PV charging power 500W AC charging power 500W Battery voltage and output voltage Battery...
Page 26: ...VA like below chart When load is larger than 1kVA 1KVA load in VA will present x xkVA like below chart Load in Watt When load is lower than 1kW load in W will present xxxW like below chart When load i...
Page 27: ...enerated this month 388kWh Load output energy this month 988kWh PV energy generated this year and Load output energy this year PV energy generated this year energy 3 88MWh Load output energy this year...
Page 28: ...n CPU version checking Main CPU version 00014 04 Secondary CPU version checking Secondary CPU version 00003 03 Bluetooth version checking Bluetooth version 00003 03 SCC version checking SCC version 00...
Page 29: ...batteries Charging by utility and PV energy Charging by utility Charging by PV energy No charging Fault mode Note Fault mode Errors are caused by inside circuit error or external reasons such as over...
Page 30: ...The unit will provide output power from the mains It will also charge the battery at line mode Charging by utility and PV energy Charging by utility Battery Mode The unit will provide output power fro...
Page 31: ...is too low 53 Inverter soft start failed 55 Over DC voltage in AC output 56 Battery is not connected 57 Current sensor failed 58 Output voltage is too low 59 PV voltage is over limitation Warning Indi...
Page 32: ...LCD setting program 33 first Then you may apply this function in device by either one of following methods 1 Setting equalization interval in program 37 2 Active equalization immediately in program 3...
Page 33: ...n voltage point the charge controller will extend the battery equalized time until battery voltage achieves battery equalization voltage If battery voltage is still lower than battery equalization vol...
Page 34: ...Loss Return Voltage 270Vac 7V Max AC Input Voltage 300Vac Nominal Input Frequency 50Hz 60Hz Auto detection Low Loss Frequency 46 56 1Hz Low Loss Return Frequency 46 5 57 1Hz High Loss Frequency 54 64...
Page 35: ...ge Capacity 2 rated power for 5 seconds Nominal DC Input Voltage 24Vdc 48Vdc Operating Range 20Vdc 34Vdc 40Vdc 66Vdc Cold Start Voltage 23Vdc 46Vdc Low DC Warning Voltage 22 5Vdc 22 0Vdc 45 0Vdc 44 0V...
Page 36: ...l Charging Current 100 50 Bulk Constant Current Absorption Constant Voltage Maintenance Floating Current Voltage T1 T1 10 T0 minimum 10mins maximum 8hrs T0 2 43Vdc 2 35Vdc 2 25Vdc Solar Charging Mode...
Page 37: ...0Hz 60Hz Auto detection Low Loss Frequency 46 56 1Hz Low Loss Return Frequency 46 5 57 1Hz High Loss Frequency 54 64 1Hz High Loss Return Frequency 53 63 1Hz Table 5 General Specifications INVERTER MO...
Page 38: ...repeatedly LCD display and LEDs are flashing Battery is disconnected Check if battery wires are connected well Buzzer beeps continuously and red LED is on Fault code 07 Overload error The inverter is...
Page 39: ...6 2400 70 188 2700 62 148 3000 56 134 Model Load VA Backup Time 48Vdc 200Ah min Backup Time 48Vdc 400Ah min 5KW 500 1226 2576 1000 536 1226 1500 316 804 2000 222 542 2500 180 430 3000 152 364 3500 130...