background image

mSquad User’s Guide 

10 

 

 
 
 

4.

 

Operation 

See the POLI User’s Guide for basic operation information for POLI multi-gas monitors.   
Special considerations for mSquad POLI monitors include: 

• 

Alarm notifications and field physical set-up 

• 

Calibration of the Head/Host unit 

• 

Wireless communication set-up in Configuration Mode and in mPower Suite 

 

4.1 Field Set-up 

Before beginning operations, the field set-up should 
be checked to ensure good wireless connection. The 
Head/Host communicates directly with each Soldier 
monitor, while communication between Soldiers 
occurs indirectly via the Head/Host. The maximum 
line-of-sight distance between a Soldier and Head is 
about 0.5 miles, and thus two Soldiers could be as far 
as 1 mile apart and still communicate. However, in 
many cases the practical operating distances are on 
the order of a few hundred yards because hills, 
buildings and other structures (especially metal and 
concrete barriers) impede wireless transmission. 
Communication can be improved by operating the 
Head unit at the highest point of the arena and/or 
placing it on a pole or other elevated structure. If a Soldier moves out of communication range 
for more than one minute, it will alarm. A quicker test of connectivity can be done by sending a 
Panic Alarm (Hold Left key for 3 seconds.) 
 

4.2 Alarm Notifications 

The POLI provides alarms including audible buzzer, visible bright LEDs, vibration, and text 
notification on the display. These can be programmed or selectively turned on or off. If an alarm 
occurs in any one unit, all units within an mSquad also go into alarm for a short period (about 15 
seconds) and then stop, but the alarm continues on the affected unit and the Head/Host until the 
alarm condition is cleared. If the alarm does not silence automatically after the issue has been 
resolved, in most cases it can be cleared by pressing the Left Key.   

4.2.1 Alarm Testing 

Under normal operation mode and non-alarm conditions, the audible (buzzer) alarm, vibration 
alarm, LED, and backlight can be tested at any time by pressing Left [+/OK] once. This alarm is 
given only on the local instrument. 

4.2.2 Gas Alarms   

When the gas concentration is outside the alarm preprogrammed Low, High, TWA and STEL 
alarm limits on any one monitor, all units within the mSquad are alarmed. The Host/Head 
displays a bell symbol 

  next to the User Name in place of the check mark to indicate a gas 

alarm, and other Soldiers display 

NAME-Gas in the top bar, where NAME is the user in 

alarm. Alarms on other Soldiers cease after about 15 seconds but the 

  continues to pulse as a 

MP400S

 

MP400S

 

MP400H

 

MP400S

 

MP400S

 

MP400S

 

MP400S

 

MP400S

 

Summary of Contents for mSQUAD MP400H

Page 1: ...mSQUAD Mobile Wireless Multi Gas Team Warning System MP400S MP400H User s Guide Rev 1 0 January 2020...

Page 2: ...t up 10 4 2 Alarm Notifications 10 4 3 Head Host Calibration 12 5 Configuration Mode 13 5 1 Navigating Configuration Mode to Edit Parameters 13 5 2 Man Down Function 14 5 3 Registering Soldier MP400S...

Page 3: ...RRATIC READING MAY INDICATE A GAS CONCENTRATION BEYOND UPPER SCALE LIMIT WHICH MAY BE HAZARDOUS ATTENTION DES LECTURES SUP RIEURES A L CHELLE PEUVENT INDIQUER DES CONCENTRATIONS EXPLOSIVES TOUTE LECTU...

Page 4: ...ions for Safe Use The POLI multi gas detector must be calibrated if it does not pass a bump test when a new sensor has been installed or at least once every 180 days depending on use and sensor exposu...

Page 5: ...by diffusion because the communications antenna is attached to the pump inlet port while MP400S Soldier units have a built in sampling pump for active gas sampling and thus a somewhat faster response...

Page 6: ...work for communication with mPower Suite configuration and data transfer software The mPower USB cable P N M 011 3003 000 is required for a PC to recognize the instrument and communicate with mPower...

Page 7: ...ration alarms 3 1 Turning On Off To turn on press and hold the Key for 3 seconds until the buzzer beeps and the red LED turns on To turn off in normal reading mode press and hold the key for a 5 secon...

Page 8: ...ength at 0 5 level Pump status pump versions only Datalogging enabled cannot turn off Battery voltage status Man down alarm enabled All sensors have been bump tested and calibrated and none are overdu...

Page 9: ...act as soft keys mapped to two text or symbol boxes at the LCD bottom that change numbers and make selections under various menus In addition to the functions described above the Left OK key can be u...

Page 10: ...est of connectivity can be done by sending a Panic Alarm Hold Left key for 3 seconds 4 2 Alarm Notifications The POLI provides alarms including audible buzzer visible bright LEDs vibration and text no...

Page 11: ...e alarm is silenced If a Soldier is turned off other Soldiers alarm immediately for 15 seconds The Host Head is alarmed with a symbol displayed next to the user name after the communication lost timer...

Page 12: ...ut the user is OK it can be stopped using the Left key Clear WARNING The Man Down feature cannot detect a worker in distress in all situations even if they have collapsed The Man Down function should...

Page 13: ...menus and OK Enter to enter a menu to edit the parameters in its submenu 5 1 1 Configuration Mode Menus and Sub menus Calibration Measurement Alarm Datalog Monitor Setup Wireless Exit Fresh Air Calib...

Page 14: ...ng the POLI to a horizontal position or pressing the Left OK key The Man Down icon on the main screen verifies that the Man Down function is enabled 5 2 2 Man Down Warn Time This menu allows adjustmen...

Page 15: ...e will appear on the Host Head Registered Device List with a next to the name The Host assigns default user names in the order they are registered e g USR00 USR01 USR02 To enter a personalized user na...

Page 16: ...vice Ping Assign Worker 1 05496868 JACK Ping Worker Assign Worker 1 05496868 JACK JACK Worker Assign Assign Worker 1 05496868 JACK BILL Worker Assign Worker Pings Monitor to Verify Unit Assign Worker...

Page 17: ...network 5 6 Channel Select the operating Channel from CH1 to CH16 Ensure that the same selection is made on the Head Host as on all Soldiers in the mSquad 5 7 mPlatoon Wireless Networks Future system...

Page 18: ...Edit the configuration parameters as desired including those under the tabs for each sensor in the upper right Click Write to upload the configuration to the instrument Read allows downloading the cur...

Page 19: ...ease of reading on the displays Click Write on the bottom of the Name panel to send the user names to the Host Head If the Write and Reset buttons are greyed out first click Read to enable them type...

Page 20: ...d Troubleshooting For maintenance and troubleshooting please see the POLI User Guide 8 mSquad Technical Specifications All specifications and listed sensors are subject to change without notice Please...

Page 21: ...mSquad User s Guide 21 Technical Support and mPower Contacts mPower Electronics Inc 3046 Scott Blvd Santa Clara CA 95054 Phone 408 320 1266 Fax 669 342 7077 info mpowerinc com www mpowerinc com...

Reviews: