ioLogik E2200 Series
Using ioAdmin
3-23
Testing DI and DO Channels
You can test each channel by opening the channel’s configuration window and selecting the Test tab.
On the Test tab, you can see how a channel’s status affects or is affected by the attached device. For DO
channels, you can set the on/off status or start and stop pulse output. For DI channels, you can monitor the
attached device’s on/off status, or monitor the counter.
Relay Count Monitoring
Two types of relay counts can be recorded in the ioLogik E2214: Total Counts and Current Counts.
Relay
Total
Counts
records how many times a Relay Output channel has been used. In general, each relay output channel
can be used an average of 1,000,000 times. Users can monitor these counts to see when the module should be
replaced, or to switch to a different channel if the total count approaches the upper limit.
Relay
Current
Counts
can be reset to zero to record the usage of the external device by monitoring the counts. For example,
if RLY-0 is connected to an external relay control board, you can monitor the current counts to see when to
replace the external relay component in advance before it fails. Last Reset Time records the time when Current
Counts was reset. Both Relay Total Counts and Relay Current Counts will be saved when there is a power failure.
The Last Reset Time will be saved only when the user manually presses the Reset to Zero button.
Summary of Contents for ioLogik E2210
Page 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Page 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Page 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Page 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...