ioLogik E2200 Series
Using the Web Console
5-11
Alias Name set
Alias Name Set
helps users configure the alias of a DI or DO channel and define the status for
on/off
to be
vice versa.
RTD Channels
On the RTD Channels page, you may view the status of all RTD channels, which includes both physical and
virtual channels.
You may click on each channel to enable or disable it, or to configure the RTD input mode. When a channel has
been disabled, the sample rate of the remaining channels will be increased automatically.
The following table is a list of supported sensor types and ranges.
Sensor Type
Degree
Count
PT50, 0.00385
-200 to 850°C
-2000 to 8500
PT100, 0.00385
-200 to 850°C
-2000 to 8500
PT200, 0.00385
-200 to 850°C
-2000 to 8500
PT500, 0.00385
-200 to 850°C
-2000 to 8500
PT1000, 0.00385
-200 to 350°C
-2000 to 3500
JPT100, 0.003916
-200 to 640°C
-2000 to 6400
JPT200, 0.003916
-200 to 640°C
-2000 to 6400
JPT500, 0.003916
-200 to 640°C
-2000 to 6400
JPT1000, 0.003916
-200 to 350°C
-2000 to 3500
Resistance (1–2200)
1 to 2200 Ω
10 to 22000
Resistance (1–1250)
1 to 1250 Ω
20 to 25000
Resistance (1–620)
1
to 620 Ω
50 to 31000
Resistance (1–310)
1 to 310 Ω
100 to 31000
Ni100, 0.00618
-60 to 250°C
-600 to 2500
Ni200, 0.00618
-60 to 250°C
-600 to 2500
Ni500, 0.00618
-60 to 250°C
-600 to 2500
Summary of Contents for ioLogik E2210
Page 138: ...ioLogik E2200 Series Cable Wiring D 4 Digital Output Sink Type...
Page 139: ...ioLogik E2200 Series Cable Wiring D 5 RTD Input Wiring Structure 2 wire 3 wire...
Page 140: ...ioLogik E2200 Series Cable Wiring D 6 Thermocouple Input Wiring Structure 2 wire...
Page 144: ...ioLogik E2200 Series Input and Output Terminal E 4 ioLogik E2262 I O left to right...