7.4.10.
Analog Menu
(Analog Output Configuration)
The setting of the F1-F2-Selection (Parameter 003) determines, which frequency (sensor1 or sensor2) is
used to generate the analog output signal.
No.
Parameter
Range
Default
078
Analog Start
(initial value of the conversion range in Hz)
:
Defines the initial frequency, at which the analog output should set
its initial value of 4 mA.
-500 000.0
-
500 000.0
(Hz)
0
079
Analog End
(final value of the conversion range in Hz)
:
Defines the final frequency, at which the analog output should set
its final value of 20 mA.
100 000
080
Analog Gain
(gain of the D/A converter in %)
:
With a setting of 100% the frequency curve between „Analog
Start“ and „Analog End“ equates to the whole stroke from 4 mA to
20 mA (thus 16 mA).
With a setting of e. g. 50 % the stroke would be only 8 mA and the
analog output only a value of 4 + 8 = 12 mA when reaching
„Analog End“.
1 - 1 000
(%)
100
0
4
8
12
16
20
mA
Analog Start (Hz)
Analog End (Hz)
A
n
a
lo
g
S
w
in
g
%
0
2
5
7
5
5
0
081
Analog Offset
(fine adjustment of the zero point in µA)
:
Accurate adjustment of the analog offset within a fine range.
-25 - 25
(µA)
0
082
Reserved
Summary of Contents for DS230 Series
Page 10: ...Ds230_03a_oi_e doc Jun 15 Page 10 100 4 3 DS236 Block Diagram 4 4 DS236 Connections...
Page 11: ...Ds230_03a_oi_e doc Jun 15 Page 11 100 4 5 DS240 Block Diagram 4 6 DS240 Connections...
Page 12: ...Ds230_03a_oi_e doc Jun 15 Page 12 100 4 7 DS246 Block Diagram 4 8 DS246 Connections...
Page 100: ...Ds230_03a_oi_e doc Jun 15 Page 100 100 12 Certificate...