9 Devices
126
Rev. 06/2021
9.2.2.4
Analog Outputs
The
Analog Outputs
button in the
Preferences
view of an added I/O communication module
opens the
Analog Outputs
view.
Note that changes in this view are not saved and applied by the I/O communication module until
you exit the view. Use the drop-down list to link the analog output of the I/O communication
module displayed in the
Ch.
(Channel) column to the following functions:
–
Not Used
The analog output input is not linked to any function.
–
Average NO
X
from NOx1 / NOx2
Output of the provisional daily average of nitrogen oxide readings converted according to
VDMA 6299:2019-09 (see section
Conversion of Nitrogen Oxide Readings
on page 42) as
determined by the respective NO
X
monitor. Scaling: 4 mA correspond to 0 mg/Nm³, 20 mA
correspond to 1,000 mg/Nm³.
–
Actual NO
X
from NOx1 / NOx2
Output of the nitrogen oxide reading currently measured by the respective NO
X
monitor con-
verted according to VDMA 6299:2019-09. Scaling: 4 mA correspond to 0 mg/Nm³, 20 mA cor-
respond to 1,000 mg/Nm³.
Summary of Contents for EasyNOx
Page 1: ...EasyNOX NOX Monitoring Operating Manual P N 01 50 026 EN Rev 06 2021 ...
Page 33: ...4 Product Description Rev 06 2021 33 4 1 7 Overview Drawings 4 1 7 1 Dimensions EasyNOX ...
Page 34: ...4 Product Description 34 Rev 06 2021 ...
Page 35: ...4 Product Description Rev 06 2021 35 CAN Bus NOX Sensor Module P N 63 05 015 ...
Page 36: ...4 Product Description 36 Rev 06 2021 I O Communication Module Optional ...
Page 142: ......