08. TROUBLESHOOTING

 INSTRUCTIONS FOR FINAL CONSUMERS

INSTRUCTIONS FOR SPECIALIZED INSTALLERS

Anomaly

Procedure

Behavior

Procedure II

Discovering the origin of the problem

• Motor

doesn't work

at all

• Make sure you

have 230Vac/24Vdc 

power in the 

automation control 

board and if it is 

working properly.

• Still not working

• Consult a qualified

MOTORLINE 

technician.

1 •

 Open control box and checkif it has 230Vac/24Vdc power supply;

2 •

 Check input fuses;

3 •

 Disconnect motor from control board and test it by connecting directly to power supply in order to find out if it has problems (see page 8B)

4 •

 If the motor work, the problem is on the control board. Pull it out and send it to our 

MOTORLINE

 technical services for diagnosis;

5 •

 If the motor doesn’t work, remove it from installation site and send to our 

MOTORLINE

 technical services for diagnosis.

• Motor

doesn’t move

but makes 

noise

• Unlock motor and

move gate by 

hand to check for 

mechanical problems 

on the gate.

Did you find 

problems?

• Consult an experienced

gate expert.

1 •

 Check all motion axis and associated motion systems related with gate and operators (pins, hinges, etc.) to find out what is the problem.

• Gate moves 

easily?

• Consult a qualified

MOTORLINE

 technician.

1 •

 Disconnect motor from control board and test it by connecting directly to power supply in order to find out if it has problems (see page 8B)

2 •

 If the motor work, the problem is on the control board. Pull it out and send it to our 

MOTORLINE

 technical services for diagnosis;

3 •

 If the motor doesn’t work, remove it from installation site and send to our 

MOTORLINE

 technical services for diagnosis.

• Motor 

opens but 

doesn’t close

• Unlock motor and

move gate by hand to

closed position. 

Lock motor(s) again 

and turn off power 

supply for 5 seconds. 

Reconnect it and send

order to open gate 

using transmitter.

• Gate opened but

didn’t close again.

1 •

 Check if there is any

obstacle in front of the 

photocells;

2 •

 Check if any of the control

devices (key selector, push

button, video intercom, etc.)

of the gate are jammed and

sending permanent signal to

control unit;

3 •

 Consult a qualified 

MOTORLINE technician.

TAll MOTORLINE control boards have LEDs that easily allow to conclude which devices are with anomalies. All safety devices LEDs (DS) in normal 

situations remain On. All "START" circuits LEDs in normal situations remain Off.

If LEDs devices are not all On, there is some security systems malfunction (photocells, safety edges), etc. If "START" circuits LEDs are turn On, there 

is a control device sending permanent signal.

A) SECURITY SYSTEMS:

1 •

Close with a shunt all safety systems on the control board (check manual of the control board in question). If the automated system starts 

working normally check for the problematic device.

2 •

 Remove one shunt at a time until you find the malfunction device .

3 •

 Replace it for a functional device and check if the operator works correctly with all the other devices. If you find another one defective, follow 

the same steps until you find all the problems.

B) START SYSTEMS:

1 •

 Disconnect all wires from START terminal input.

2 •

 If the LED turned Off, try reconnecting one device at a time until you find the defective device.

NOTE:

If the procedures described in sections A) and B) don’t result, remove control board and send to our technical services for diagnosis.

• Motor

doesn’t make

complete 

route

• Unlock motor and

move gate by 

hand to check for 

mechanical problems 

on the gate.

• Encountered

problems?

• Consult an experienced

gate expert

1 •

 Check all motion axis and associated motion systems related with gate and operators (pins, hinges, etc.) to find out what is the problem.

• Gate moves 

easily?

• Consult a qualified

MOTORLINE

 technician.

1 •

 Check if the limit microswitches are adjusted for the required course.

2 •

 Disconnect motor from control board and test it by connecting directly to power supply in order to find out if it has problems (see page 8B)

3 •

 If the motor doesn’t work, remove it from installation site and send to our 

MOTORLINE

 technical services for diagnosis.

4 •

 If motors work well and move gate at full force during the entire course, the problem is from controller. Set force using trimmer on the board. 

Make a new working time programming , giving suffient time for opening and closing with appropriate force (see manual of the controller in 

question).

NOTA:

Setting force of the controller should be sufficient to make the gate open and close without stopping, but should stop with a little effort from a 

person. In case of safety systems failure, the gate shall never cause physical damaged to obstacles (vehicles, people, etc.).

Summary of Contents for TELICA

Page 1: ...V3 2 REV 05 2020 TELICA EN USER S AND INSTALLER S MANUAL...

Page 2: ...ystems This marking on the product or literature indicates that the product and electronic accessories eg Charger USB cable electronic material controls etc should not be disposed of as other househol...

Page 3: ...perienced in terms of usage of the product in a safe manner and who understands the risks and dangers involved Children shouldn t play with the product or opening devices to avoid the motorized door o...

Page 4: ...all safety conditions have been met In the event of tripping of circuits breakers of fuse failure locate the malfunction and solve it before resetting the circuit breaker or replacing the fuse If the...

Page 5: ...230V Power supply 24Vdc 230Vac Power 220W 380W Force 200 Nm Working frequence Intensive Use 50 Capacitor 12 5 F Protection grade IP54 Noise LpA 50dB A Thermal protection 120 C Operating temperature 2...

Page 6: ...r malfunction Fig 5 To unlock insert the unlock key into the automation front hole and turn it on clockwise 4 5 times until you feel a limit To lock Rode a chave no sentido contr rio at sentir um ob s...

Page 7: ...ion and open the door leaf to the desired position 2 Loosen A the opening ring screw and turn it B until you hear a click of the micro switch 3 Tighten the screw C of the ring to lock it in this posit...

Page 8: ...echanical stoppers in the opening and closing position of the gate If not respected components of the automation may suffer efforts for which they were not prepared and as a result will be damaged It...

Page 9: ...it is possible to understand if the automatism can function properly connected directly to the current You should use a new capacitor during this test to ensure that the problem does not lie on it 1 C...

Page 10: ...al systems NOTES To make these tests it isn t necessary to remove it from the location where it is installed be cause in this way you can understand of the automatism works properly directly connected...

Page 11: ...de which devices are with anomalies All safety devices LEDs DS in normal situations remain On All START circuits LEDs in normal situations remain Off If LEDs devices are not all On there is some secur...

Page 12: ...tor 2 Motor 2 starts closing before Motor 1 It must be applied an 8 capacitor in each motor on the opening and closing wires as explained above NOTE If any one of the motors moves in the wrong way jus...

Page 13: ...C2 230Vac 2Ah 115Vac 3Ah N0 N0 EN 09 CONNECTION SCHEME Complete opening Partial opening Flashing light 12 24VD 4W M x Transformer 230Vac or 110Vac 5 0 60Hz 120W M x Solar Panel Electric lock 12 24VDC...

Reviews: