User Interface
4-24 Manual # 42-02-2P24
• DOOR HOLD INPUT TIMER (Range: 0-240 Seconds)
• Timer used only if there is a DHLD (Door Hold) input to the controller (
). A Door Hold Open button is usually connected to this
input. Timer determines how long the doors will stay open when the door hold open
button is pressed. The timer is canceled and the doors will begin to close if either the
Door Close button or a Car Call button is pressed. If a Door Hold Key switch (instead of
a button) is connected to the DHLD input, timer value should be set to zero so that the
doors will close immediately when the switch is turned OFF.
• PARKING DELAY TIMER (Range: 0.0-6.0 Minutes)
• Used only if a parking floor is selected. Timer starts when car is free of call demand.
The car will park after the timer expires.
• FAN/LIGHT OUTPUT TIMER (Range: 5.0-20.0 Minutes)
• Used with the FLO output, this timer sets the amount of time that will pass before the
FLO output is activated to shut off the car light and fan. Time will start when the car
becomes inactive. The FLO output is typically connected to a relay that turns OFF the
fan and light in the car. This is also used for PI Turned Off if No Demand.
• HOSPITAL EMERGENCY TIMER (Range: 1.0-10.0 Minutes)
• Sets the amount of time the car will remain at the hospital emergency floor with the
doors open before automatically returning to normal service. (
EMERG. OPERATION?” on page 4-45
• DOOR OPEN PROTECTION TIMER (Range 8 - 30 Seconds)
• Determines how long the door operator will attempt to open the doors. If DOL does
not go low within this time, the doors will begin to close.
• PASSWORD TIMER (Range: 0 - 30 Seconds)
• Determines length of time the car will wait for correct password entry through car call
COP buttons after a secured car call has been requested before cancelling the call entry
cycle. (Applies only to BSI security.)
• CTL DOOR OPEN TIMER (Range: 2.0 - 60.0 seconds)
• Used to specify how long the doors should remain open after car returns to lobby when
the CTL (Car to Lobby) input is activated.
• DOOR BUZZER TIMER (Range: 0 - 30 Seconds)
• Determines length of time door buzzer sounds before doors are automatically closed.
• OPN/CLS INTRLOCK TIMER (Range: 050ms - 950ms, 50ms increments)
• Introduces a delay when closing or opening doors are abruptly reversed (i.e., photo eye
activation, door button press, etc.). This may be required if the door operator is sensi-
tive to such reversal due to de-bounce capability.
• Set to NONE if unnecessary.
• FIRE PH1 RECLOSE TIMER (Range: Disabled or 1 - 120 seconds)
• If set to a value other than NONE, the doors will close after the set number of seconds
following a Fire Service Phase 1 recall. Doors may be opened using in-car or hall door
open buttons.
Summary of Contents for Motion 4000
Page 20: ...xiv Manual 42 02 2P24 5 20 13 ...
Page 38: ...Motion 4000 Traction Elevator Control 1 18 Manual 42 02 2P24 ...
Page 178: ...Final Adjustments 3 56 Manual 42 02 2P24 ...
Page 322: ...User Interface 4 144 Manual 42 02 2P24 ...
Page 391: ...PC Board Quick References 5 69 5 Motion 4000 Figure 5 11 Example MC CPI Wiring ...
Page 439: ...Customer Notations A 27 A Motion 4000 Customer Notations Table A 4 Customer Notation Area ...
Page 444: ...Appendix A 32 Manual 42 02 2P24 ...