User Interface
4-16 Manual # 42-02-2P24
• SERIAL CARTOP DOOR CONTROL?
• Set to Yes if the door operator is connected to an HC-UIO board in the cartop box
rather than using multiple connections through the traveler to the HC-CTL board in
the controller cabinet.
• DISABLE LOCAL HALL CALLS?
• Set to Yes if the car is dispatched by a group controller and should not respond to a
local (connected to car) riser. If this car has swing operation, do not set this to Yes as it
will prevent the car from responding to local riser calls.
Fire Service Menu Options
• FIRE SERVICE OPERATION?
• If Fire Service operation is not required, set to NO. If set to YES, the options below will
appear.
• FIRE PHASE 1 MAIN FLOOR
• Any landing may be the Main Fire Return Floor for Fire Service.
• FIRE PHASE 1 ALT. FLOOR
• Any landing may be the Alternate Fire Return Floor for Fire Service.
• FIRE SVCE. CODE
• Fire Service Operation will conform to the selected fire service code. Available codes
are:
1. CHICAGO (OLD)
9.
CITY OF HOUSTON
2. VET ADMIN (Veterans' Administration)
10. AUSTRALIA
3. NYC RS-18
11. CITY OF DETROIT
4. ANSI A17.1 -89>
12. MASSACHUSETTS
5. CALIF. TITLE 8
13. ANSI A17.1 85 - 88
6. HAWAII
14. CITY OF DENVER
7. CSA B44-M90
15. CHICAGO 2001
8. 34 PA CODE, CH. 7
16. ANSI A17.1-2000
• FIRE PHASE I 2ND ALT. FLOOR
• Detroit Fire Code only. Any landing may be the 2
nd
alternate fire return floor.
• Select None if there is no second alternate return floor.
• WILL THIS CAR RUN ON PH2?
• If set to yes, this car is allowed to run on Fire Phase II.
• BYPASS STOP SW. ON PHASE 1?
• Prevents the stop switch from being bypassed on Fire Phase I. When set to NO, the
CSB output will not come ON as the car is returning on Fire Phase I.
Summary of Contents for Motion 4000
Page 20: ...xiv Manual 42 02 2P24 5 20 13 ...
Page 38: ...Motion 4000 Traction Elevator Control 1 18 Manual 42 02 2P24 ...
Page 178: ...Final Adjustments 3 56 Manual 42 02 2P24 ...
Page 322: ...User Interface 4 144 Manual 42 02 2P24 ...
Page 391: ...PC Board Quick References 5 69 5 Motion 4000 Figure 5 11 Example MC CPI Wiring ...
Page 439: ...Customer Notations A 27 A Motion 4000 Customer Notations Table A 4 Customer Notation Area ...
Page 444: ...Appendix A 32 Manual 42 02 2P24 ...