Morrison Bros. Co.  ‑  Dubuque, IA  ‑  800‑553‑4840

174‑‑‑0101 PP

!

!

Maintenance Instructions on Back

The 174 Series valves are designed where maximum pressure control is needed such as bypassing a pump in 

order to reduce the pressure at the outlet. 

Failure to follow any or all of the warnings and instructions in this document could result in a hazardous 

liquid spill, which could result in property damage, environmental contamination, fire, explosion, serious 

injury, or death.

Installation

Warnings

• 

Fire Hazard

 – Death or serious injury could result from spilled liquids. 

•  Install in accordance with all applicable local, state, and federal laws.

•  For your safety, it is important to follow local, state, federal and/or OSHA rules that apply to working inside, 

above, or around the storage tank and piping area. Use all personal protective equipment required for 

  working in the specific environment.

•  Piping could be under pressure. Liquid and vapors may be expelled from the piping, valves or fittings while 

performing installation. Liquids and vapors could catch fire or cause an explosion. 

Avoid

 sparks, open flame, 

or hot tools when working on valves.

Steps

1. Inspect valve for shipping damage. Do not use if valve is damaged. Call 

Morrison Bros. Co. for assistance.

2. Inspect valve openings for foreign matter such as packaging material. 

Remove any that is found.

3. Prior to mounting the valve in the piping, verify the intended direction of 

liquid flow. The valve inlet and outlet are marked on the appropriate hex 

where the piping connects.

4. Apply a non-hardening, fuel resistant thread sealant to the male threads 

of the pipe. When threading the valve onto the piping, and the piping into 

the valve, make certain to wrench on the valve hex closest to the end you 

are threading. Connect piping to valve inlet and outlet and complete the 

rest of the piping.

5. You may now introduce liquid to the valve. Inspect the valve and piping 

for leaks. Repair as is necessary.

6. If you wish to adjust the opening setting of the valve, remove the lock 

cap on the valve by loosening the single cap screw and slipping off the 

lock cap.(See Fig. 1.) This will expose the adjustment screw. (See Fig. 

2.) To change the opening setting, loosen the lock nut on the adjustment 

screw and turn the adjustment screw. Clockwise turning will increase the 

opening setting. Counter-clockwise turning will decrease the opening 

setting. There is string packing used to seal around the adjustment 

screw. This may need to be replaced after making adjustments. It can 

be purchased from Morrison Bros. Co. Once you have achieved your 

desired setting, tighten the lock nut on the adjustment screw and replace 

the lock cap. 

Fig. 174 By-Pass Valve

Installation & Maintenance Instructions

FIGURE 1

LOCK 

CAP

 CAP

SCREW

FIGURE 2

ADJUSTMENT 

SCREW

LOCK NUT

BONNET

GASKET