MORNINGSTAR CORPORATION
17
3.0
Figure 2. Removing the Battery Select jumper.
Load Control – Low Voltage Disconnect / Reconnect
Choose between two (2) load control
Low Voltage Discon
-
nect
/
Reconnect
settings.
SWITCH 2 OFF (
↓):
LVD = 11.50 V, LVR = 12.60 V
SWITCH 2 ON (
↑)
:
LVD = 11.00 V, LVR = 12.10 V
2
(2) These values can be modified with custom programming. See
Section 4.7
Programming Custom Setpoints
for more information
.
Enable or Disable Auto-Equalization
Turn the auto-equalize feature OFF or ON. The auto-
equalize feature will administer an equalization charge
(flooded battery type only) every 28 days or if the battery
discharges too low the previous night. There is no
equalization charge for the gel or sealed battery type.
SWITCH 3 OFF (
↓)
:
AUTO-EQUALIZE OFF
SWITCH 3 ON (
↑)
:
AUTO-EQUALIZE ON
(agm,
flooded
battery type only)