ZX1Se
ZX2Se
ZX5Se ZX10Se
Document No.996-182-000-1, Revision 01
user manual
Page 1: ...ZX1Se ZX2Se ZX5Se ZX10Se Document No 996 182 000 1 Revision 01 user manual...
Page 2: ...re 9 5 2 FAULT CONDITIONS 9 5 2 1 Fault Indication 9 5 2 2 User Actions 9 5 3 FIRE ALARM CONDITIONS 9 5 3 1 Fire Alarm Indications 9 5 3 2 User Actions 9 5 4 USER OPTION FUNCTIONS 10 5 4 1 Test 10 5 4...
Page 3: ...1 ZX1SE ZX2SE CONTROLS AND DISPLAYS 3 FIGURE 2 ZX5SE ZX10SE CONTROLS AND DISPLAYS 3 FIGURE 3 SYSTEM CONTROL LED DISPLAY 4 Table of Tables TABLE 1 CONTROL KEY FUNCTIONS 3 TABLE 2 ALPHANUMERIC AND INTER...
Page 4: ...Control Panels are 1 1 2 1 5 and 1 10 loop panels for use with analogue addressable devices from the following detector manufacturer ranges Apollo S90 Hochiki Morley IAS Nittan System Sensor 1 2 Warni...
Page 5: ...n the Zone LED Displays indicate the location of any fire alarm or fault and the alphanumeric display gives more detailed fire alarm or fault information At USER LEVEL 1 all the displays are functiona...
Page 6: ...ZX2Se Controls and Displays Figure 2 ZX5Se ZX10Se Controls and Displays Alphanumeric Display System Status LED Display Control Keys Program Interactive Keys Zone LED Display Key Legend Symbol Function...
Page 7: ...bled at USER LEVEL 1 Pressing the SHIFT key will cause the display to prompt for entry of the Level 2 password The password must be entered to re enable the control keys at Level 2 3 2 Front Panel LED...
Page 8: ...programmed system delays are currently stopping some outputs from operating Follow defined evacuation procedure The delays may be enabled or disabled Refer to Disablement Function Relays Disabled Yel...
Page 9: ...essing the SHIFT key will show a list of optional functions or prompt for the level 2 password 03 Mar 2007 11 38 All devices are within working limits Panel ACTIVE Control Keys INHIBITED 1 Do you want...
Page 10: ...panel is operating only on batteries that are in good condition this gives the incorrect indication that the batteries are not serviceable 2 Under very poor battery conditions but with a good mains su...
Page 11: ...Test 3 Time 1 4 Enable 5 Disable 6 Print 7 View If a key has not been pressed for a certain period the display will revert to the normal Level 1 display showing the system status message To re show th...
Page 12: ...fter correcting the problem press the SYSTEM RESET key The FAULT and other appropriate system status LED Indicators will be turned off The alphanumeric display returns to normal mode 5 3 Fire Alarm Co...
Page 13: ...t the relay and sounder outputs connected to the system This test is only available to Level 3 users Audible Indicator To test the internal buzzer a short beep is emitted Time To change the date and t...
Page 14: ...l display after 1 minute Pressing SHIFT or will return the display to the test display The display will then prompt for whether the sounder outputs should ring 03 Mar 2007 11 38 All devices are within...
Page 15: ...he panel is then ready to test the next detector Note Up to 30 seconds is allowed for smoke detectors to clear If an alarm signal is received from a zone other than those under test then all sounder o...
Page 16: ...ted The first six outputs are reserved for the panel s own onboard relay and sounder circuits as shown below Output 1 Onboard Relay 1 Output 2 Onboard Relay 2 Output 3 Onboard Sounder A Output 4 Onboa...
Page 17: ...e time at the Master Panel All of the other panels will synchronize their date and time to that of the master panel when a reset is performed on the master panel 5 4 3 Enable Disable Functions To sele...
Page 18: ...ut devices in the zone including smoke temperature and call points When a zone is disabled the DISABLEMENT LED and the corresponding yellow Zone FAULT LED will be illuminated If the panel is part of a...
Page 19: ...ll devices are within working limits CPU __ Enter the address of the required panel The display will then prompt for the loop and device address information as described above 5 4 3 3 Enable or Disabl...
Page 20: ...The day after tomorrow the panel will go immediately into a full fire alarm condition on receiving a high signal from a device The number of days can be selected in the range 001 to 199 To permanently...
Page 21: ...ys Select option 6 from the Enable or Disable menus If disable delays is selected the display prompts for entry of the Level 2 password to confirm 03 Mar 2007 11 38 All devices are within working limi...
Page 22: ...nu press NO to return to the main options menu The following View Mode Options are available View Option Description of Function 1 Devices Displays the status and text of anyone detector on a signalli...
Page 23: ...al buzzer will sound The sensor location together with a warning that the panel has entered stage 1 of a delayed alarm and a request to enter the stage 2 period to allow a search to take place will be...
Page 24: ...nel MORLEY IAS 7 Level 3 Programmer Functions Level 3 functions are for service engineer or installation company use only and therefore are not covered by this manual User Manual Document No 996 182 0...
Page 25: ...eal and false fire alarms faults pre alarm warnings tests temporary disconnection s and service visits A brief note of any work carried out or outstanding should be made Sample pages of the logbook ar...
Page 26: ...Fire Alarm Control Panel MORLEY IAS EVENT DATA Date Time Counter Reading Event Action Required Date Completed Initials Table 7 Logbook Event Data User Manual Document No 996 182 000 1 Revision 01 Page...
Page 27: ...MORLEY IAS ZX Fire Alarm Control Panel Page 24 Document No 996 182 000 1 Revision 01 User Manual NOTES...
Page 28: ...MORLEY IAS All rights reserved The MORLEY IAS Logo is a registered trademark MORLEY IAS Fire Systems Charles Avenue Burgess Hill West Sussex RH15 9UF England Web site www morleyias co uk...