www.miinet.com
Moore Industries-International, Inc.
- 5 -
User’s Manual
225-748-01L
February 2017
STA (HLPRG) Quick Start Guide
Use the front pushbuttons to quickly and easily set-up the STA for your application. After
programming your alarm using the diagram below, install the unit into your application using the
connection diagrams and terminal designation table located in this manual.
The STA configuration can be recorded using the worksheet found at the end of this manual.
Please contact Moore Industries Sales for an interactive version of the worksheet.
Front Panel
Pushbuttons
Use the UP and DOWN pushbuttons to scroll through menus and
sub-menus. Use the SELECT pushbutton to access menus and/or
make a choice.
Trim Analog Output:
Connect the STA into a calibration
set-up as shown in the manual,
trim the analog output
Set Trim Zero, Full,
Factory Trim and Test.
(
Requires -AO Option
)
Password:
View or change password.
Configure Options:
Display mode, decimal places,
50/60Hz filter, startup delay, display test
and factory reset.
CONFG
OPTNS
TRIM
AOUT
Reset Fault:
Reset fault option,
select “Yes” or “No”.
CONFG
PASWD
Exit Configuration Menu:
Return to process display.
CONFG
EXIT
D
D
U
CONFG
ALARM
Configure Alarm:
Settings for Alrm 1, Alrm 2, Input Fault*, and Manual Reset*.
Set trip point, dead band, high/low trip, latching/non-latching,
Enter Delay*, and Manual Reset Configuration*.
D
SCALE
AOUT
Scale Analog Output:
Set the values for output at
zero and full input
(
Requires -AO Option
)
D
U
RESET
FAULT
D
D
U
CONFG
AOUT
Configure Analog Output:
Select volt or current output.
Choose damping value
and fail mode.
(
Requires -AO Option
)
TRIM
INPUT
Trim Input:
Select Trim Mode, User 1 PNT,
User 2 PNT, or FCTRY TRIM
D
U
U
U
D
U
U
U
D
U
ENTER
PASS
SYS
LOCK
Enter the password
code to enable
settings changes.
(Default = 1)
(
If the incorrect password is entered,
access to the configuration menus is denied.)
Configure Input:
Choose Input type,
Input Zero, Input Full, Input OOR*,
and BWIRE Level
Security Jumper
installed in Full
Access position.
Security Jumper
installed in No
Access position.
Security Jumper
installed in Password
Required position.
CONFG
INPUT
SELECT
DOWN
UP
SCALE
INPUT
D
D
Scale Input:
Set the Scale Mode On/Off, set EGU, set Zero values,
and set Full values.
WARNING:
This menu is intended to aid in the configuration of your instrument.
However, proper use of the STA at its intended safety level cannot be
achieved without thorough review of the STA in Safety Instrumented
Systems Section of this manual.
* For STA units with firmware versions 1.4 and earlier, these Settings are not configurable.
Programmable Current/Voltage Safety Trip Alarm
STA
HLPRG
SEC
TION 1