26
Rev. 1.0
10/19/2018
SSDC-A Hardware Manual
400-820-9661
3.2
Digital Outputs
Y1, Y2, Y3 and Y4 Digital Outputs
•
Y1 can be configured as alarm signal output. It can also be configured as static in position
signal output(static, checking in position when motor is stopped) ,or as dynamic in position
signal output (dynamic, checking in position all the time.)
•
Y2 can be configured as Tach signal output, tach output produce pulsed relative to the motor
position with configurable resolution. It can also be configured as static in position signal
output(static, checking in position when motor is stopped) ,or as dynamic in position signal
output (dynamic, checking in position all the time.),or as Timing signal output(50 pulses per
rotation)
•
Y3 can be configured as signal output to release brake. It can also be configured as static in
position signal output(static, checking in position when motor is stopped) ,or as dynamic in
position signal output (dynamic, checking in position all the time.)
•
Y4 can be configured as static in position signal output( static, checking in position when motor
is stopped) ,or as dynamic in position signal output (dynamic, checking in position all the time.)
Y1, Y2, Y3 and Y4 can be configured by Step-Servo Quick Tuner.
The chats below show how to connect to the output:
NOTE: Do not connect the outputs to more than 30VDC power supply.
And the current of each output terminal must not exceed 100mA.