background image

42

Appendix

XG0229 - 112718

(1)  Revise NFPA-54 section 10.5.4.2 by adding a second exception as 

follows:

 

Existing chimneys shall be permitted to have their use continued 
when a gas conversion burner is installed, and shall be equipped 
with a manually reset device that will automatically shut off the 
gas to the burner in the event of a sustained back-draft.

(2)  Revise 10.8.3 by adding the following additional requirements:

(a)  For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 
or in part for residential purposes, including those owned 
or operated by the Commonwealth and where the side wall 

exhaust vent termination is less than seven (7) feet above 

finished grade in the area of the venting, including but not 
limited to decks and porches, the following requirements shall 
be satisfied: 

1.  INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time 

of installation of the side wall horizontal vented gas fueled 
equipment, the installing plumber or gas fitter shall observe 
that a hard wired carbon monoxide detector with an alarm and 
battery back-up is installed on the floor level where the gas 
equipment is to be installed. In addition, the installing plumber 
or gas fitter shall observe that a battery operated or hard wired 
carbon monoxide detector with an alarm is installed on each 
additional level of the dwelling, building or structure served by 
the side wall horizontal vented gas fueled equipment. It shall be 
the responsibility of the property owner to secure the services of 
qualified licensed professionals for the installation of hard wired 
carbon monoxide detectors
a.  In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or an attic, the hard 
wired carbon monoxide detector with alarm and battery back-
up may be installed on the next adjacent floor level.

b.  In the event that the requirements of this subdivision can 

not be met at the time of completion of installation, the 
owner shall have a period of thirty (30) days to comply with 
the above requirements; provided, however, that during said 
thirty (30) day period, a battery operated carbon monoxide 
detector with an alarm shall be installed.

2.  APPROVED CARBON MONOXIDE DETECTORS. Each carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2042 listed 

and IAS certified. 

3.  SIGNAGE. A metal or plastic identification plate shall be 

permanently mounted to the exterior of the building at a 
minimum height of eight (8) feet above grade directly in line with 
the exhaust vent terminal for the horizontally vented gas fueled 
heating appliance or equipment. The sign shall read, in print 

size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.

Appendix C: Amendment 

(Gas Fireplace / Equipment sold in the State of Massachusetts)

5.08: Modifications to NFPA-54, Chapter 10

4.  INSPECTION. The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve 
the installation unless, upon inspection, the inspector observes 
carbon monoxide detectors and signage installed in accordance 
with the provisions of 248 CMR 5.08(2)(a)1 through 4. 
(b)  EXEMPTIONS: The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4: 

1.  The equipment listed in Chapter 10 entitled “Equipment Not 

Required To Be Vented” in the most current edition of NFPA 54 as 
adopted by the Board; and 

2.  Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from the 
dwelling, building or structure used in whole or in part for 
residential purposes.
(c)  MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING 

SYSTEM PROVIDED. When the manufacturer of Product 
Approved side wall horizontally vented gas equipment 
provides a venting system design or venting system 
components with the equipment, the instructions provided 
by the manufacturer for installation of the equipment and the 
venting system shall include:

1.  Detailed instructions for the installation of the venting system 

design or the venting system components; and

2.  A complete parts list for the venting system design or venting 

system. 

(d)  MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING 

SYSTEM NOT PROVIDED. When the manufacturer of a 
Product Approved side wall horizontally vented gas fueled 
equipment does not provide the parts for venting the flue 
gases, but identifies “special venting systems”, the following 
requirements shall be satisfied by the manufacturer:

1.  The referenced “special venting system” instructions shall 

be included with the appliance or equipment installation 
instructions; and 

2.  The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 
parts list and detailed installation instructions. 

(e)  A copy of all installation instructions for all Product Approved 

side wall horizontally vented gas fueled equipment, all venting 

instructions, all parts lists for venting instructions, and/or all 

venting design instructions shall remain with the appliance or 
equipment at the completion of the installation.

(3)  After NFPA-54 section 10.10.4.2 add a new section 10.10.4.3 as 

follows:

 

When more than four gas appliances are to be vented through a 
common gas vent or common horizontal vent manifold, a plan of 
the proposed vent installation shall be submitted to the Inspector 
and the serving gas supplier for review and approval.

Extraction from: Massachusetts Rules and Regulations
5.00: Amendments To 2002 Edition Of ANSI Z223.1-NFPA-54

Summary of Contents for H38CLNI-2

Page 1: ...HL38PRNI 2 NG Linear HL38PRLI 2 Propane Read and understand this manual Improper installation adjustment alteration service or maintenance can cause serious injury property damage or even death For assistance or additional information consult a qualified installer service agency or the gas supplier A barrier designed to reduce the risk of burns from the hot viewing glass is provided with this appl...

Page 2: ... will be voided by and Montigo disclaims any responsibility for the following actions Modification of the fireplace and or components including Direct Vent assembly or glass doors Use of any component part not manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual Consult your local Gas Inspection Branch on install...

Page 3: ... 21 Section 5 2 Gas Pressure 21 Section 5 3 GAS CONNECTION 21 PFC Gas line access 21 PRC Gas line access 21 Section 6 Finishing 22 Mantels Surrounds 22 Fireplace Facing 22 Finishing around the fireplace 22 Flush Finishing the Fireplace 22 Section 7 Screen Installation and Removal 23 Removing the Screen 23 To Install Screens 23 Replacement Screens 23 Section 8 Installing Removing the Door 24 Removi...

Page 4: ...ons mustconformtothelocalcodesor intheabsenceoflocalcodes to the current version of Canadian Electrical Code CSA C22 1 1 Installations in the USA must conform to the local codes or in the absence of local codes to the current version of National Fuel Gas Code ANSI Z223 1 NFPA 54 Electrical installations must conform to the local codes or in the absence of local codes to the current version of the ...

Page 5: ...ntaining proper clearance Firestops installed Exteriorwall roofflashinginstalledandsealedincompliancewithlocalbuildingcode Terminations installed and sealed in compliance with local building code Direct vent termination is highest point in vent assembly Wiring Electrical Section 4 Unswitched power provided to the appliance PPO box Low voltage wire connected to dry contact wall switch non powered G...

Page 6: ...ng Plate Sample Figure 1 1 Rating Plate for IPI electronic ignition Figure 1 2 Rating Plate for IPI electronic ignition LBA12xx ANSI Z21 88 2016 Rating Plate Label LB1223 V5 0 SIT IPI with screen JUN 16 2014 Teklynx LabelView Demo ...

Page 7: ...8 68 2 1 2 34 1 1 2 29 1 1 8 235 9 1 4 67 2 5 8 H38DF PRC HL38DF PRC DIMENSIONS TOLERANCES ARE IN METRIC MM 1 6 MM IMPERIAL FRACTIONAL 1 16 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED PROPRIETARY AND CONFIDENTIAL November 30 2017 DATE 1007...

Page 8: ... 14 3 16 114 4 1 2 844 33 1 4 GAS SUPPLY H38DF CR HL38DF CR DIMENSIONS TOLERANCES ARE IN METRIC MM 1 6 MM IMPERIAL FRACTIONAL 1 16 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED PROPRIETARY AND CONFIDENTIAL November 29 2017 DATE ...

Page 9: ...ombustible Framing for shelves over the fireplace Rear vent Figure 3 b Combustible Framing for shelves over the fireplace Top vent Figure 3 b Combustible Framing for shelves over the fireplace Top vent Figure 3 b Non Combustible Framing with alcove above fireplace Top Vent 24 1 2 40 3 4 44 41 23 3 4 44 COMBUSTIBLE SHELF EXTERIOR WALL EXTERIOR WALL EXTERIOR WALL EXTERIOR WALL COMBUSTIBLE SHELF COMB...

Page 10: ...ent Shelf over the fireplace Top vent Alcove above the fireplace Figure 3 b Combustible Framing for shelves over the fireplace Rear vent Figure 3 b Combustible Framing for shelves over the fireplace Top vent Figure 3 b Non Combustible Framing with alcove above fireplace Top Vent EXTERIOR WALL NON COMBUSTIBLE STUD INCLUDED WITH UNIT EXTERIOR WALL COMBUSTIBLE SHELF NON COMBUSTIBLE FACING NON COMBUST...

Page 11: ...to a ceiling within the fireplace enclosure Note For mantel clearance please refer to Section 6 Finishing The 4 nailing flange extension is shipped attached to the top edge of the fireplace see Figure 1 The nailing flange extension may be substituted with a piece of NON Combustible material of the same thermal characteristics ie cement board or equivalent to fit the opening This is recommended in ...

Page 12: ...cations to ensure the planned termination location is acceptable Once the termination location has been established refer to the appropriate section below for installation details All fireplaces shipped from the factory are top vent Silicone application is NOT required when joining Montigo vent pipes and components Section 3 1 Converting top rear vent Use the following instructions to convert a un...

Page 13: ...or a more detailed diagram of allowed termination locations see Appendix A A maximum of two offsets each offset is made up of 2 90 bends may be made for vertical vent runs Firestops must be installed as required by National local codes Ensure all horizontal runs are supported with a minimum of 3 supports per 10 of venting Install all roof flashing and storm collars as shown Figure 6 Top vent roof ...

Page 14: ...lation XG0229 112718 Figure 6 d Side vent Roof mounted venting 1 90 bend Storm collar Support plate 32 max Roof flashing PVTK1 Termination Support ring PEXT Solid Sections 2 min 12 max Firestop Firestop 90 Elbow ...

Page 15: ... the interior side of the studs concrete or finished wall construction using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here from the inside and attach to the MOSR by installing a min quantity of 4 bolts into the threaded nuts on the MOSR Frame Installation of termination frame at time of framing in masonry Terminations with a BSR frame allow the installation of th...

Page 16: ... wall flange of the termination Plot on the Venting Graph with an X If the X falls on or above the top boundary of the shaded area the installation is acceptable TOP VENT RUN Example A Acceptable Installation If the vertical dimension from the hearth is 114 and the horizontal run to the wall flange of the vent termination is 168 this would be an acceptable installation Example B Unacceptable Insta...

Page 17: ...from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 84 this would not be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termination is 144 this would not be an acceptable installation PFC Rear Venting Graph Measure the vertical...

Page 18: ...n from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 84 this would not be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termination is 144 this would not be an acceptable installation PRC Rear Venting Graph Measure the vertic...

Page 19: ...ireplace flue collar to the wall flange of the termination Plot on the Venting Graph with an X If the X falls on or above the top boundary of the shaded area the installation is acceptable TOP VENT RUN Example A Acceptable Installation If the vertical dimension from the hearth is 126 and the horizontal run to the wall flange of the vent termination is 138 this would be an acceptable installation E...

Page 20: ...the vertical dimension from the hearth is 66 and the horizontal run to the wall flange of the vent termination is 84 this would not be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termination is 144 this would not be an acceptable installation Corner Rear Venting ...

Page 21: ...A 08A 12 58DVA 16A 20 5DLT 12 5DLS1 12 5DLT2 20 5DSL2 20 5DAL 3 to 10 Rigid Telescopic Pipe 58DVA 17TA 58DVA 24TA 5DLA30 Elbows 5 8 Vent PEL 90MM m m 90º PEL 90FF f f 90º PEL 90FM f m 90º PEL 45FM f m 45º 58DVA E30 30 58DVA E45 45 58DVA E60 60 58DVA E90 90 5DE45 45 5DE90 90 5D45L 45 5D90L 90 Support Ring Plate PSPXT 8 58DVA DC 5CS Firestop FS 8 58DVA WFS 58DVA FS 5CS 5DFS Roof Flashing PRF 7 1 12 ...

Page 22: ...er section from the outside of the structure To complete the installation fasten the Heat Shield Outer Section Termination frame to the structure Figure 15 e RHS101 Installation Figure 15 c RHS101 Installation Install by sliding Outer Section over vent pipe where it passes through the combustible construction Figure 15 a RHS8 Installation Install by sliding over vent pipe where it passes through t...

Page 23: ...ot Assembly Pilot Electrical Harness Connector Honeywell Gas Control SV9501M Gas Control Connector Junction Box 115VAC 24VAC 40 VA Transformer Black White Green Gnd Screw Wall Switch Fan Plug Receptacle BLACK LED LIGHTS LED1 RED LED LED2 AMBER LED MAIN Power 120vac 60 hz 6 amps 3 15A FUSE WHITE GREEN SPARK SENSOR BLUE OPTIONAL CPI IPI SWITCH WHITE MAIN ON OFF SWITCH GAS CONTROL KNOB INLET PRESSURE...

Page 24: ...ially recovered as heat into the building so it does not use as much energy as running a pilot in the off season A connector is supplied with this unit that can be plugged into the wire harness connected to the controller This jumper cable gives the Remote Control the ability to operate the CPI IPI switch and set the unittooperateineithercondition CPImeans ContinuousPilotIgnition or Standing Pilot...

Page 25: ...put system follow the appropriate local codes for your area DO NOT connect the fireplace to pressures in excess of 1 2lb This will damage the gas control valve Figure 18 Pressure Requirements Figure 18 b Gas Inlet Supply location PFC Gas line access PRC Gas line access CL CR Gas line access NOTICE 996 39 3 16 1007 39 5 8 102 4 1072 42 3 16 630 24 13 16 152 6 565 22 1 4 644 25 3 8 518 20 3 8 204 8 ...

Page 26: ...mantel will rise above normal room temperature and walls above fireplace may be hot to touch Side wall clearances are 3 Combustible surrounds may be installed with 3 clearance to the side of the fireplace as shown Flush Finishing the Fireplace A noncombustible finishing material may be installed over the face of the unit as shown below Please be aware that the temperature of the fireplace face wil...

Page 27: ...n gas fireplaces are extremely hot while the fireplace is on and remain hot even after the fireplace has been turned off Safety screens are mandatory and can reduce the risks of severe burns Please keep children away from the fireplace at all times CAUTION NOTICE Screen Bottom Tabs Screen Tab Receptacles Upper Screen Studs Upper Screen Stud Catch Left Side Detail Left Side Detail Removin The Safe ...

Page 28: ...STEP 7 Grasp the door on either side usually midway and lift upward lift the door carefully up and away from the front of the fireplace Place the door aside in a safe place while maintenance and or cleaning is being performed Removing the door The doors are removed in a few simple steps Follow these below to remove the horizontal access panel unlatch the door buckles and remove the door Replace in...

Page 29: ...f LOG A LOG B LOG C LOG D LOG D LOG A LOG B LOG C Section 9 Installing the Accessories WARNING This appliance is intended for use only with the included Montigo burners and accessories Never install or add any additional or alternative media rock wool or other material in this appliance The use of additional or alternative materials may pose potential safety hazards damage to the appliance and voi...

Page 30: ...OFF unless knob is pushed in slightly Do not force Standing Continuous Pilot Ignition SIT 820 with American Flame Electronic Ignition For Your Safety READ BEFORE LIGHTING C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempt to repair may result in a fire ...

Page 31: ...truction guide 8 After completion of the information in the Troubleshooting section Repeat step 5 9 If the system will not function correctly follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier 1 STOP Read the safety information above on this label 2 Remove the lower Horizontal access panel 3 Turn ON manual ON OFF switch located below the horizonta...

Page 32: ...oflame 2 Control Module 4 Wiring Harness 5 Variable Speed fans If applicable 7 Proflame 2 remote control 8 Battery Pack 9 Manual override switch NOTE Can not be used with home automation systems SW1 Programing Button LED1 Red Diagnostic Light LED2 Amber Programing Remote Control Light Blue back lit LCD display On Off key Thermostat key Up Down arrow key Mode key Not Used Not Used CPI mode optional...

Page 33: ...ur 4 times to indicate transmitter s command is accepted The System is now initialized Temperature Indication Display With the system in the Off position press the Thermostat Key and the Mode Key at the same time Look at the LCD screen on the Remote Control to verify that a C or F is visible to the right of the Room Temperature display Turn On the Fireplace With the system Off turn the master over...

Page 34: ...o show that the room thermostat is On and the set temperature is now displayed To adjust the set temperature press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter Smart Thermostat Remote Control Operation The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actu...

Page 35: ...s to turn on off or adjust the fan speed A single beep will confirm reception of the command Disabling Thermostat Some jurisdictions and bedroom installations require the thermostat to be disabled 1 Partially take out one battery see Figure 27k 2 Insert the battery while holding down the thermostat button The remote screen will display Clr while the button is held down See Figure 27l 3 To enable t...

Page 36: ...non abrasive non ammonia based glass cleaners One of the most effective products is Kel Kem During the initial firing Silicone seals will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed using normal household products Use a vacuum cleaner or whisk broom to keep the control compartment burner and firebox free from dust and lint Figure 28 ...

Page 37: ...le limits Pilot lights but Main burner will not Light and igniter continues to spark 1 Check the Pilot Flame Sensor Rod and clean with steel wool or similar 2 Check the Pilot hood and clean with steel wool if dirty 3 Adjust pilot flame using the pilot adjustment screw if the pilot flame is too long or too short Flame should fully engulf the sensor rod and must be stable 4 Check and make sure the g...

Page 38: ... SCREENS A Revision A 12 01 2014 DWG NO MATERIAL DIMENSIONS ARE IN INCHES FRACTIONAL TWO PLACE DECIMAL THREE PLACE DECIMAL ALL BENDS ARE ASSUMED UNLESS NOTED OTHERWISE DATE NAME THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED PROPRIETARY AND C...

Page 39: ...mbustion air inlet to other appliance for appliance 100 000 BTU H 30 KW 12 inches 12 inches M clearance to forced air supply inlet 6 feet 3 feet above air inlet N clearance above paved sidewalk or paved driveway located on public property 7 feet 7 feet P clearance under veranda porch deck or balcony 22 inches to combustibles 16 inches to non combustibles 22 inches to combustibles 16 inches to non ...

Page 40: ... gas NG or liquefied petroleum LP only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the appliance produce excessive temperatures will result in a fire hazard and void all warranties This warranty is transferable The appliance must remain in its original place of installation to be valid If the components of the appliance covered by this warran...

Page 41: ...ritten consent of The Companies The Companies shall in no event be responsible for any warranty work done without first obtaining the Companies written consent The Companies employees and dealers have no authority to make any warranties to neither alter this warranty nor authorize any remedies in addition to or inconsistent with those stated within this warranty IF WARRANTY SERVICE IS NEEDED To ma...

Page 42: ...The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Appendix C Amendment Gas Fireplace Equipment sold in the State of Massachusetts 5 08 Modifications to NFPA 54 Chapter 10 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon ...

Page 43: ...43 Notes XG0229 112718 ...

Page 44: ...XG0229 112718 Installation Maintenance Manual PENINSULA PANORAMA CORNER Indoor direct vent Gas Fireplace ...

Reviews: