Design
17
Configure module address
Up to three XC-NET-DP-M (PROFIBUS-DP) or XC-NET-CAN
(CANopen) modules can be used in any combination. Reserve a
memory area for each module in the CPU by defining a module
address for each one:
Set address on the device
X
Set the address for each module with the aid of the jumpers in
the jumper block range from 13 to 19 (
a
following diagrams).
Setting the address in XSoft
Assign the input/output address range (%IB/%QB) to the modules
in the PLC configuration in XSoft. The modules are integrated in
turn into the PLC configuration:
X
Assign the memory range beginning with start address CE000
to the first module (CANopen or PROFIBUS-DP) to be
configured.
The input/output devices assigned to this module are connected to
the module bus system via address CE000.
X
Assign the memory range beginning with start address CC000
generally to the second module, and the address range D4000
to the third module.
Bus termination resistors
Bus termination resistors must be provided at both ends of the
cable.
1.
r
CE000*
Figure 18 : Address setting of module 1
* Factory setting
2.
r
CC000
Figure 19 : Address setting of module 2
3.
r
D4000
Figure 20 : Address setting of module 3
1 1 0
19 18 17 16 15 14 13
0 1 1 1
1 1 0
19 18 17 16 15 14 13
0 1 1 0
1 1 0
19 18 17 16 15 14 13
1 0 1 0
Figure 21 : Example configuration with three modules and the
assigned addresses
h
When using the ZB4-209-DS2 PROFIBUS plug, the bus
termination resistor can be enabled or disabled via the
slide switch on the plug.