Fault-finding
33
11/06 AWB1251-1590GB
Fault-finding
In addition to the diagnostic messages in the PROFIBUS-DP
(
section “Diagnostic data”, page 26) the LEDs on the
SmartWire modules and on the PROFIBUS-DP gateway can
be used to trace the fault.
Table 15: Error messages
No.
Part
Event
Explanation
Remedy
1
Gateway
SmartWire LED
flashing
Configuration of
the unit is not
correct
• Check plug
connection
• Press configuration
button after
exchange of device
SWIRE-DIL or
SWIRE-4DI-2DO-R
Ready LED
flashing
Follwomng
SmartWire modules
Ready LED pulse
flashing
2
Gateway
Ready-LED OFF
Internal error
Exchange gateway
PROFIBUS LED
ON or flashing
3
Gateway
Ready LED
flashing
No PROFIBUS-DP
communication
available
Check the
PROFIBUS-DP
connection
PROFIBUS LED
OFF
4
Gateway
Ready LED
flashing
PLC in STOP
Switch PLC to RUN
PROFIBUS LED
ON
5
Gateway
Ready LED
flashing
PROFIBUS-DP
configuration or
SmartWire
configuration
incorrect
Check configurations
PROFIBUS LED
flashing
6
Gateway
U-Aux-LED OFF
No voltage on the
U-Aux terminal
Check the power
supply, wiring and
fusing for the supply
voltage to the contactor
coils