Monitoring of lower current limit
Table 8:
Monitoring of lower current limit
Diagnostic status through AS-Interface
®
parameter
channel
Table 9:
Diagnostic status through AS-Interface
®
parameter channel
h
On RA-MO up to version 2.1 this function is set with the
jumpers,
a
table 3 on page 61.
pole 9
Middle
jumper
Configuration for RA-MO…
from version 2.2
0
right
Monitoring of lower current limit disabled
(factory setting)
1
right
Monitoring of lower current limit enabled
only in manual mode
0
left
Monitoring of lower current limit enabled
only in automatic mode
1
left
Monitoring of lower current limit enabled in
both manual and automatic modes
h
On RA-MO up to version 2.1 this function is set with the
jumpers.
pole 10
Configuration for RA-MO… from version 2.2
0
Diagnostic status through AS-Interface
®
parameter
channel and I/O error signal disabled (factory setting).
1
Diagnostic status through AS-Interface
®
parameter
channel and I/O error message enabled.