System Rapid Link
01/08 AWB2190-1430GB
22
X
Tighten all seven contact screws. This makes the contact with
the conductors.
Observe the permissible tightening torque. The installation of the
flexible power supply and busbar junction is now completed. All
that remains is to fit the plug of the Rapid Link function modules
RA-…/C1 or the cover RA-C1-COV and secure it with the clips.
X
Now connect the cables to the securely screw-fitted power feed
unit sing screw terminals. According to DIN EN 60947 all cable
types (flexible, solid or stranded) can be connected.
X
Fit the sealing cap.
X
Fit the screw covers.
Removing
Disassembly is in reverse order of assembly; see section
“Establishing connections”, page 21.
The flexible busbar’s insulation must not be damaged. Insulate any
points that have been opened by the insulation piercing terminals
using an approved insulation tape (Scotch VM from 3M) and
observing the manufacturer’s instructions about correct insulation.
End pieces and bushings
Once the flexible busbar has been laid, all free cable ends must be
safely terminated and sealed to IP65. To do this, use the cable end
pieces or bushings. Cable end pieces consist of a shorter lower and
a longer upper section, which contains the the seal and the
insulation channels.
With bushing RA-C1-DF you can feed the flexible busbar into
power supply and distributor module RA-C1-VM-7 or a control
panel.
j
Warning!
Turn the contact screws in all the way to the stop! The
tightening torque must not exceed 1 Nm.
We recommend the use of an electrical or pneumatic
torque wrench. Phillips (cross-head) screwdriver, size: 1.
Shaft length at least 45 mm.
i
Attention!
Never connect or disconnect the plug under load!
h
For flexible conductors the use of ferrules is
recommended. At a cross-section of 4 mm
2
the ferrules
must be assembled in a square.
h
Attention!
If you do not connect round cables, seal the round cable
outgoer with a blanking plug.
h
If a contact screw breaks, the cable feeder must be
replaced with a new one and refitted adjacent to the
original one offset by at least 200 mm.
h
Attention!
Observe the applicable safety instructions. Never work on
live equipment.
Summary of Contents for Rapid Link
Page 10: ...01 08 AWB2190 1430GB 6 ...
Page 40: ...01 08 AWB2190 1430GB 36 ...
Page 48: ...01 08 AWB2190 1430GB 44 ...
Page 70: ...01 08 AWB2190 1430GB 66 ...
Page 146: ...01 08 AWB2190 1430GB 142 ...
Page 162: ...01 08 AWB2190 1430GB 158 ...