Speed controller RA-SP
01/08 AWB2190-1430GB
126
F-06, F-07 time ramps (ACC, DEC)
Acceleration time 1 defines the time in which the motor reaches its
end frequency after a start signal is issued.
Deceleration time 1 defines the time in which the motor
decelerates to 0 Hz after a Stop signal.
During operation, a changeover from the time ramps set under
PNU F02 and F03 to those programmed under PNU A92 and A93
can be performed. This can take place when the fixed frequencies
defined with PNU A95 and A96 are reached.
PNU
Designation
Adjustable in
RUN mode
Value
Function
FS
F02
Acceleration
time 1
j
0,1 to 3000 s
Resolution of 0.1 s at an input of 0.1 to 999.9
Resolution of 1 s at an input of 1000 to 3000
10,0
PNU
Designation
Adjustable in
RUN mode
Value
Function
FS
F03
Delay time 1
j
0.1 to 3000 s
Resolution of 0.1 s at an input of 0.1 to 999.9
Resolution of 1 s at an input of 1000 to 3000
2
Figure 122: Time ramp
t
1
: Acceleration time 1
t
2
: Acceleration time 2
PNU A95
PNU A95
t
1
t
2
f
t
Summary of Contents for Rapid Link
Page 10: ...01 08 AWB2190 1430GB 6 ...
Page 40: ...01 08 AWB2190 1430GB 36 ...
Page 48: ...01 08 AWB2190 1430GB 44 ...
Page 70: ...01 08 AWB2190 1430GB 66 ...
Page 146: ...01 08 AWB2190 1430GB 142 ...
Page 162: ...01 08 AWB2190 1430GB 158 ...