Description of parameters
applicable to RA-SP
123
Description of parameters applicable to RA-SP
F-00 transition frequency (F-BASE)
The base frequency is the frequency at which the output voltage
has its maximum value.
F-01 End frequency (F-MAX)
To define another constant-voltage frequency range that lies
beyond the transition frequency (F-00), use PNU A04. This end
frequency (F-01) must not be smaller than the transition
frequency.
F-37
MONITOR
C23
Not used with RA-SP
A-F
F-38
INIT
Initialization
INIT SEL
EUR
b85
Software initialization
EUR
= 01
Note: Other settings are not permissible for RA-SP!
Caution:
Do not change!
EUR
INIT DEBG
OFF
C91
Reserved (indication error)
Caution: Do not change setting!
OFF
INIT DOPE
FWD
F04
Direction of rotating field
FWD
INIT MODE
TRP
b84
Intialization mode
TRP
F-43
PID
PID regulation
PID SW
OFF
A71
Not used with RA-SP
Caution:
Do not change!
OFF
PID P
1.0
A72
1,0
PID I
001.0s
A73
1,0
PID D
000.0
A74
0,0
PID CONV
01.00
A75
1,00
PID INPT
CUR
A76
CUR
DEX-KEY-10
Fn No./indication
DF5
PNU
Meaning
(display code DF5)
Value range
FS
a
Page
PNU
Designation
Adjustable in
RUN mode
Value
FS
A03
Base frequency
–
50 to 360 Hz
50
Figure 120: End frequency (
f
1
= transition frequency,
f
2
= end
frequency)
PNU
Designation
Adjustable in
RUN mode
Value
FS
A04
End frequency
–
50 to 360 Hz
50
i
Caution!
The operation of a motor at speeds higher than the rated
speed (see nameplate) can cause mechanical damage to
the motor (bearings, unbalance) and the machinery to
which it is connected and can lead to dangerous
operating conditions!
0
f
1
f
2
100
[%]
U
f
[Hz]
A004
A003