01/02 AWB8230-1415GB
Analog outputs –
AM, AMI and FM
59
Current output (AMI)
The AMI terminal provides the variables listed in the table below
in the form of a 4 to 20 mA current signal.
X
In PNU C029, specify the variable which the AMI terminal is to
provide.
X
In PNU C087, specify the gain factor and in PNU C088 the
offset.
Frequency output (FM)
The FM terminal provides the variables listed in the table below in
the form of a pulse-width modulated (PWM) signal (
a
Fig. 47).
An exception is the output frequency to which the value “03” is
assigned which is output as a frequency modulated (FM) signal
(
a
Fig. 49).
X
In PNU C027, specify the variable which the FM terminal is to
provide.
X
In PNU B081, specify the gain factor.
PNU
Function
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C029
Output, AMI
terminal
–
j
00
Output frequency: 0 Hz to end frequency PNU A004
(
a
Section “Maximum end frequency“, Page 125)
00
01
Output current: 0 to 200 %
02
Torque: 0 to 200 %
04
Output voltage: 0 to 100 %
05
Inverter input power: 0 to 200 %
06
Thermal load ratio: 0 to 100 %
07
Ramp frequency: 0 Hz to end frequency PNU A004
(
a
Section “Maximum end frequency“, Page 125)
C087
Gain, AMI
terminal
j
j
0 to 255
Current output gain
80
C088
Offset, AMI
terminal
j
j
0 to 20 mA
Current increase
0.0
PNU
Function
Adjustable in RUN mode
Value
Function
WE
Normal
Extended
C027
Output, FM
terminal
–
j
00
Output frequency, PWM signal
00
01
Output current
02
Torque: for SLV, 0 Hz SLV and vector control only
03
Output frequency: FM signal
04
Output voltage
05
Inverter input power
06
Thermal load ratio
07
Ramp frequency
b081
Gain, FM
terminal
j
j
0 to 255
Gain of the frequency output
60