Mains choke
Figure 174: DE4-LN... mains chokes
h
When the frequency inverter is working at its rated current
limit, the mains choke causes a reduction of the frequency
inverter’s maximum output voltage (
U
2
) to about 96 % of
mains voltage (
U
LN
).
DV6-340-
Mains current
(
I
LN
) of the DV6
without mains
choke
Assigned
mains choke
075
2.8
DE4-LN3-075
1K5
4.2
DE4-LN3-2K2
2K2
5.8
DE4-LN3-3K0
4K0
9.5
DE4-LN3-4K0
5K5
13
DE4-LN3-7K5
7K5
18
DE4-LN3-11K
11K
25
DE4-LN3-15K
15K
35
DE4-LN3-15K
18K5
42
DE4-LN3-22K
22K
53
DE4-LN3-30K
30K
63
DE4-LN3-45K
37K
83
DE4-LN3-45K
45K
99
DE4-LN3-55K
55K
121
DE4-LN3-75K
75K
164
DE4-LN3-90K
90K
194
DDK3,2-9,2
110K
239
DDK4,0-9,2
132K
286
DDK4,0-9,2
h
For technical data for the DE4-LN series mains chokes, see
installation instructions AWA8240-1711, for those of the
DDK series, refer to the main Industrial Switchgear cata-
logue.
h
Mains chokes reduce the magnitude of the current harmo-
nics up to about 30 % and increase the lifespan of
frequency inverters and upstream-connected switching
devices.